Purge Switch Open During Purge Check Instructions
6. The unit should begin its start sequence, then shut down and display
PRG SWITCH OPEN
DURING PURGE.
7. Replace the wire on the
Purge
switch and depress the
CLEAR
button. The unit should
restart.
Figure 5-10a: Air/Fuel Valve Cover Location
– BMK 1500 – 3000
Figure 5-10b: Air/Fuel Valve Cover Location
– BMK 750/1000
AIR/FUEL VALVE COVER
(Rotate Counter-Clock-Wise
to Remove)
AIR/FUEL
VALVE
BLOCKED
INLET
SWITCH
BLOWER PROOF
SWITCH
AIR/FUEL VALVE COVER
(Rotate counter-clockwise to
remove)