Trouble shooting
Page 51 / 51
Protective functions
Cause
Description
Message
During con-
stant speed
OC. Drive
Deceleration
OC. Decel
Acceleration
OC. Accel
Overcurrent
protection
When the output of the inverter is
short circuited, the motor is
locked, or a heavy load is
suddenly applied, and the inverter
output current exceeds a
predetermined level, the inverter
is shut off.
At the others
Over. C
Overload
protection
When a motor overload is detected by the electronic
thermal function, the inverter is shut off
Over. L
Breaking resistor
overload
When the allowable relative duration for the V2000
built-in breaking unit entered under
b 90
is
exceeded, the inverter will be shut off
OL. BRD
When the inverter DC bus voltage exceeds a
predetermined level due to regenerative energy from
the motor, this trip occures and the inverter is shut
off.
Over. V
Overvoltage
protection
100s after the input power supply voltage has
exceeded the allowable voltage limit, the output
voltage will be switched off.
OV. SRC
EEPROM error
When the inverter memory has a problem due to
noise
or excessive temperature rise, this trip occurs and
the inverter is shut off.
EEPROM
Undervoltage
protection
A decrease of DC bus voltage may result in
improper function of the control unit. It may also
cause motor heating and low torque. The inverter is
shut off when the DC bus voltage goes below a
certain level.
Under. V
CT error
If the V2000 built-in current transformer is not
functioning properly, the inverter will be shut off.
CT
CPU1
CPU error
Malfunction or abnormality of the CPU.
The inverter is shut off.
CPU2
External trip
A trip signal from external equipment shuts off the
inverter. It is necessary to assign the external trip to
an intelligent input terminal.
EXTERNAL
USP error
Indicates an error when power is turned on while the
inverter run is enabled (when USP function is
selected).
USP
Ground fault
protection
The inverter is protected by detection of ground
faults between the drive output and the motor at
power on. Protection is for the inverter only and not
for humans.
GND. Flt
Thermal
protection
When the temperature of the inverter module is
beyond specification, the thermal sensor in the
inverter module detects the temperature and the
inverter is shut off.
OH FIN
PTC error
When the resistance value of the external
thermistor is too large, the equipment detects the
abnormal condition of the thermistor and then
shuts off the inverter (when PTC function is
selected).
PTC