Wiring
Page 27 / 51
The following table shows the location and dimensions of all terminals:
002NFE,
004NFE
007NFE~022NFE
004HFE~040HFE
055HFE, 075HFE
Terminal type
Screw
Width
(in
mm)
Screw
Width
(in
mm)
Screw
Width
(in
mm)
Power terminal
M3.5
7.1
M4
9
M5
13
Control terminal
M2
-
M2
-
M2
-
Alarm terminal
M3
-
M3
-
M3
-
Grounding terminal
M4
-
M4
-
M5
-
L
5
4
3
2
1 P24
H
O OI
L FM
CM2
12 11
AL0 AL
1
AL
2
6
Location of control terminals
Location of
alarm terminals
In the following table the purpose of the power terminals is shown:
Terminal
symbol
Purpose
Description
L1(L1), L2,
L3(N)
Mains supply
Single phase supply: connect to L1, N
Three phase supply: connect to: L1, L2, L3
U, V, W bzw.
T1, T2, T3
Inverter output
Connect a three phase motor
+1, +
External DC
reactor
Normally a short bar is attached between
ter1 and +. When a DC reactor is to
be connected, remove the short bar first.
+, RB
External rege-
nerative resistor
An optional regenerative resistor can be
connected here.
+, -
Braking unit
Connect the optional braking unit (when high
braking torque is required).
Grounding
Ground must be connected to prevent electric
shock should the inverter case carry
dangerous voltages due to a malfunction.
L1
(L1)
L2
L3
(N)
U
(T1)
V
(T2)
W
(T3)
Motor
The following table lists the tightening torque values for tightening the screws:
Screw
Torque in Nm
M2
Typ. 0.20 Max. 0.25
M3
Typ. 0.50 Max. 0.60
M3.5
Typ. 0.80 Max. 0.90
M4
Typ. 1.20 Max. 1.30
M5
Typ. 2.00 Max. 2.20
The following table describes the function of each control terminal:
(
continued on next page
)
Terminal
category
Sym-
bol
Purpose
Initial setting
Remarks
6
2. Acceleration/deceleration
Reset
5
Reset
2. Acceleration/deceleration
4
Multistage frequency input /
USP function
3
Multistage frequency input /
use 4-20mA input
2
Reverse run
1
These inputs have different purposes
depending on the user programmed
configuration:
Forward and reverse running
command, up to 4 multistage speed
settings, jogging run, 2nd stage
acceleration/decel., free run stop,
external trip, USP function, terminal
software lock, reset, PTC, input for
choosing current as analog set value
Forward run
Input closed (ON):
Function active
Input opened (OFF):
Function not active
Input must be ON for a
minimum of 12ms
Digital
Inputs
P24
Common for input signals
24V DC; max. 30mA