The functions of group C are used for configuring the programmable digital inputs and outputs.
Function
Display *)
Function description / parameter setting range
Standard
setting
Set
values
Programmable digital inputs
Digital inputs 1, 2, 3, 4, and 5 can be assigned 15 different input functions. Every input can be assigned to any of the
15 input functions with the exception of the thermistor input function (parameter 19) which can only be assigned to
input 5. However, two different digital inputs can not be assigned the same input function.
The inputs can be programmed either as normally closed contacts or as normally open contacts (the only exception
is the digital input configured as RS, this input can not be programmed as normally closed contact).
Function of
digital input 1
C 01
N
The programmable digital inputs (control terminals 1 through 5)
can be assigned one of the following functions:
00: FW (start/stop forward run)
01: RV (start/stop reverse run)
02: CF1 (1. multistage frequency input)
03: CF2 (2. multistage frequency input)
04: CF3 (3. multistage frequency input)
05: CF4 (4. multistage frequency input)
06: JG (jogging run)
09: 2CH (2. acceleration/deceleration)
11: FRS (free run stop)
12: EXT (external trip)
13: USP (restart prevention function)
15: SFT (software lock)
16: AT (use input OI)
18: RS (reset)
19: PTC thermistor input (only digital input 5)
00
Function of
digital input 2
C 02
N Refer to
C 01
for possible parameters
01
Function of
digital input 3
C 03
N Refer to
C 01
for possible parameters
FE model
02
FU model
16
Function of
digital input 4
C 04
N Refer to
C 01
for possible parameters
FE model
03
FU model
13
Function of
digital input 5
C 05
N Refer to
C 01
for possible parameters
18
Type of digital input
1
C 11
N 00: Normally open contact 01: Normally closed contact
00
Type of digital input
2
C 12
N Refer to
C 11
for possible parameters
00
Type of digital input
3
C 13
N Refer to
C 11
for possible parameters
00
Type of digital input
4
C 14
N Refer to
C 11
for possible parameters
FE model
00
FU model
01
Type of digital input
5
C 15
N Refer to
C 11
for possible parameters