Wiring
Page 24 / 51
90
°
-angle
Mains circuit power cable
(L1, L2, L3(N), U, V, W, RB, +1, +, -
)
Signal line (H, O, OI, L, FM, 1,
2, 3, 4, 5, 11, 12, CM2, P24)
Separate by 10cm or more
-
Do not short circuit the terminals P24 and L, H, OI, or FM by mistake, because this may cause
a malfunction.
-
Do not short circuit the terminals H and L because this may cause a malfunction.
The following figure shows an example for connecting a driver-IC to the digital inputs when using
the inverter´s internal 24VDC power supply terminal (left half of figure below) and when using a
separate external 24VDC power supply (right half of figure below).
L1 (L1)
L2
L1 (L1)
T1 (U)
T2 (V)
T3 (W)
1
2
3
4
5
L
P24
AL0
AL1
AL2
Motor
+1
+
1
2
3
4
5
S
COM
-
1
2
3
4
5
L
P24
1
2
3
4
5
S
COM
6
6
6
6
V2000 s
er
ies
fr
equency inve
rt
er
Alarm
terminals
Transistor output driver
YTS48 or similar
24VDC
(
Note
)
Note
: Do not short circuit the terminals P24 and L by mistake because this may lead to a malfunction.
Terminals for
braking unit
24VDC
(
Note
)
24V
battery
V2000 s
er
ies
fr
equency inve
rt
er
(
ter
m
inals
not s
how
n her
e
are exact
ly
li
ke t
hose of
the
inv
er
te
r s
how
n in the
le
ft par
t of this
figur
e)
.
Transistor output driver
YTS48 or similar
Wiring equipment and options
CAUTION Provide the wiring equipment in accordance with the safety codes required
by jurisdictional authorities. If specified in standards or laws and regulations,
follow their istructions. In the following table some guidelines for choosing an
appropriate wire gauge are presented:
Cable specifications
Motor
output
(kW)
Inverter
model
Power lines
Signal
lines
600V fuse to be used
(rated current / A)
0.2
V2000-002NFE
0.4
V2000-004NFE
0.55
V2000-005NFE
1.5 mm
2
(AWG 15)
10 A
0.75
V2000-007NFE
1.1
V2000-011NFE
2.5 mm
2
(AWG 13)
16 A
1.5
V2000-015NFE
4.0 mm
2
(AWG 11)
25 A (single phase)
16 A (three phase)
2.2
V2000-022NFE
4.0 mm
2
(AWG 11)
40 A (single phase)
25 A (three phase)
0.4
V2000-004HFE
1.5 mm
2
(AWG 15)
Sh
ie
ld
ed
wi
re
(m
a
10 A
Содержание V2000 Series
Страница 1: ...INVERTER Series V2000 M A N U A L NB588XA...