INVERTER
Series
V2000
M A N U A L
NB588XA
Страница 1: ...INVERTER Series V2000 M A N U A L NB588XA...
Страница 2: ...ides you with the information necessary to install start up and operate the V2000 frequency converters It is recommended that this manual is read thoroughly before powering up the frequency converter...
Страница 3: ...e mail watt sued t online de WATT DRIVE Nord GmbH D 51429 Bergisch Gladbach Vertriebs und Servicecenter K ln Tel 49 2204 84 2800 Fax 49 2204 84 2819 e mail watt koeln t online de WATT DRIVE D 97044 W...
Страница 4: ...s ore protrusions at or above line potential Extreme care should be taken to protect against shock For these reasons the following safety guidelines should be observed Stand on an insulating pad and m...
Страница 5: ...quirements reccommendations and safety messages highlighted in this manual must be strictly complied with NOTES ON EMC ELECTRO MAGNETICAL COMPATIBILITY WARNING This equipment should be installed adjus...
Страница 6: ...1 024 V2000 022 NFE 1 220V 10 thru 240V 5 UHZNF E 1 024 V2000 004 HFE UHZNF F 3 007 V2000 007 HFE UHZNF F 3 007 V2000 015 HFE UHZNF F 3 007 V2000 022 HFE UHZNF F 3 007 V2000 030 HFE UHZNF F 3 011 V20...
Страница 7: ...x and the motor housing and carefully remove this paint if necessary 4 Very frequently interference is coupled in through installation cables This influence you can minimize Lay interfering cables sep...
Страница 8: ...8 2800 1978 1978 Dimensions single wire litze 4 4 mm 4 4 mm 4 4 mm 4 4 mm 4 4 mm 4 4 mm Output cable 3x1 5mm 3x1 5mm 3x2 5mm 4x1 5mm 4x2 5mm 4x2 5mm Weight in kg approx 0 5 0 7 1 0 0 8 1 1 2 4 Heat di...
Страница 9: ...on 20 7 Wiring 21 Wiring the power supply and motor 21 Wiring the control terminals 22 General remarks 23 Wiring equipment and options 24 Terminals 26 8 General operation notes 29 Before starting oper...
Страница 10: ...s well as places with dust corrosive gas explosive or inflammable gas grinding fluid mist salt damage etc Otherwise there is a danger of fire CAUTION The wall surface on which the inverter is mounted...
Страница 11: ...While being energized don t open the front case Otherwise there is a danger of electric shock WARNING Never operate the switches with wet hands Otherwise there is a danger of electric shock WARNING If...
Страница 12: ...connectors e g from fans and printed circuit boards never pull the attached wires Otherwise there is a danger of fire due to wire breakage and or injury Others CAUTION Withstand voltage tests and ins...
Страница 13: ...frame with as short a wire as possible Grounded piping or shielded wire Addition of an EMI filter on the input side of the inverter also reduces the effect of noise from commercial power lines on exte...
Страница 14: ...cation label are described below In the illustration below the contents of the model designation used for V2000 series inverters is explained UHGV2000 004 H F E 5 Inverter series Version number _ 1 2...
Страница 15: ...130 10 5 129 7 2 5 D C B A 98 110 4 118 130 5 156 7 6 D C B A 5 Air Air Fan 140 180 15 3 7 3 5 D C B A 128 168 10 5 140 C B A 5 Air Air 128 5 168 180 164 7 D 6 Fan Legend A Control terminals B Alarm t...
Страница 16: ...perator Via keys RUN for start and STOP RESET for stop Default setting forward run Forward Reverse run Start Stop Ext signals Intelligent input terminals configurable as FW and RV Intelligent input te...
Страница 17: ...fault setting forward run Forward Reverse run Start Stop Ext signals Intelligent input terminals configurable as FW and RV Intelligent input terminals programmable as FW Forward run start stop RV Reve...
Страница 18: ...1 Digital operator can be opened Note 2 Serial interface Screw Note 2 Control terminals Grounding terminal PE Grounding terminal PE Control terminals Alarm terminals Rear cover Mains circuit terminals...
Страница 19: ...R COVER CONTROL TERMINALS MAINS CIRCUIT TERMINALS ALARM TERMINAL KEY COVER OPENED CASING COOLING FIN SERIAL INTERFACE DIGITAL OPERATOR CAN BE OPENED Anm 2 KEY COVER CONTROL TERMINAL MAINS CIRCUIT TERM...
Страница 20: ...he figure are only meant for reference A more compact installation back to back may well be possible and should be discussed with WATT DRIVE Please always leave enough room for the key cover to be ope...
Страница 21: ...pulse current sensitive earth leakage circuit breakers which have a short term delay and a higher trigger current 500mA should be used Other components should be secured with separate earth leakage c...
Страница 22: ...L3 N Connect three phase power supply 50 60Hz to terminals L1 L2 L3 N 5 Don t remove the short bar between the terminals 1 and Wiring the control terminals The following figure shows the location of t...
Страница 23: ...therwise the surge voltage created when the relay goes on or off may damage the output circuit Be sure that the specified grounding is carried out Separate the inverter s grounding pole from those of...
Страница 24: ...e terminals P24 and L by mistake because this may lead to a malfunction Terminals for braking unit 24VDC Note 24V battery V2000 series frequency inverter terminals not shown here are exactly like thos...
Страница 25: ...4 0 mm 2 AWG 11 4 0 mm 2 AWG 11 16 A 25 A 25 A 25 A 4 0 mm 2 AWG 11 25 A Notes Field wiring connections must be made by a UL listed and CSA certified closed loop terminal connector sized for the wire...
Страница 26: ...ithout inverter by power lines An AC reactor installed between inverter output and motor smoothens motor run and so reduces torque ripple When the cable between the inverter and the motor is too long...
Страница 27: ...e is required Grounding Ground must be connected to prevent electric shock should the inverter case carry dangerous voltages due to a malfunction L1 L1 L2 L3 N U T1 V T2 W T3 Motor The following table...
Страница 28: ...ts can be user programmed to provide different signals for the following situations Signal when reaching set value or passing a configurable frequency signal during motor run overload signal PID devia...
Страница 29: ...y parameter must be chosen in accordance with the maximum frequency of the connected motor and machine 10 Do not operate the inverter with the front case opened Make sure the front case is completely...
Страница 30: ...g the test run due to overcurrent or overvoltage increase acceleration or deceleration time Notes on technical specifications Note 1 Protective structure is based upon EN60529 Note 2 The applicable mo...
Страница 31: ...supply three phase 50 60 Hz Remove short bar if the inductor is connected Set value input 4 20 mA Analog set value 0 10V Pot 1k 2k Ohm A trip will occur when a running command is active at the time th...
Страница 32: ...g A 92 and A 93 is activated FRS 11 Free run stop function When the terminal FRS is activated frequency to the motor is switched off and the motor runs free EXT 12 External trip When the terminal EXT...
Страница 33: ...l is output as long as the output frequency is held constant at set value With a digital output being configured as FA2 a signal will be output as long as the actual output frequency is above the valu...
Страница 34: ...s not function and the lamp is off The lamp is on when this key is available PRG Lamp This lamp is on while a parameter is being set RUN Lamp This lamp is on when the inverter is running or the run co...
Страница 35: ...rward or reverse run STOP key This key stops the L100 inverter When a trip occurs this key becomes the RESET key Group H exten ded functions Setting parameters for extended functions example for exten...
Страница 36: ...s in the range of 0 1 through 999 9 Resolution 1s in the range of 1000 through 3000 10 0 Deceleration time 1 F 03 Y Setting range 0 1s 3000s Resolution 0 1s in the range of 0 1 through 999 9 Resolutio...
Страница 37: ...reaction to changes in set value 8 Extensive filtering slow reaction to changes in set value 8 Function Display Function description parameter setting range Standard setting Set values Multistage freq...
Страница 38: ...the stop command is issued By applying a strobed DC voltage to the motor s stator a braking torque is induced into the rotor that effectively works against the rotation of the motor Usage of the DC br...
Страница 39: ...the proportional gain kp the integral gain TN and the differential gain TV of the control algorithm can be set independently from each other The set value and the actual value are scaled in setting r...
Страница 40: ...5 Although these gains can be set independently of each other there are interactions between them When the P gain kp is changed the effective I gain changes TN also Only when kp 1 the effective I gai...
Страница 41: ...be reduced under A 45 to the rated motor voltage Example With a mains supply voltage of 440V and a motor rated voltage of 400V the parameter 440 has to be entered under A 82 and 91 400 440 100 has to...
Страница 42: ...igured acceleration time 03 After the time set under b 03 has elapsed the inverter synchronizes to the motor s current speed and the motor is decelerated using the configured deceleration time Afterwa...
Страница 43: ...the configured overload limit is reached the frequency will be reduced within the time entered here setting range 0 1s Hz 30s Hz Important note Do not enter values below 0 3 1 0 Function Display Funct...
Страница 44: ...row keys and the FUNC key simultaneously While holding down the keys mentioned above press the STOP key shortly and wait about 3 seconds for the LED display to show the message d 00 in a blinking mann...
Страница 45: ...t stop forward run 01 RV start stop reverse run 02 CF1 1 multistage frequency input 03 CF2 2 multistage frequency input 04 CF3 3 multistage frequency input 05 CF4 4 multistage frequency input 06 JG jo...
Страница 46: ...put terminal can be used to output one of the following values 00 Output frequency display analog signal 0 10VDC 01 Motor current display analog signal 0 10VDC 100 of the rated current corresponds to...
Страница 47: ...heating and low torque The inverter is shut off when the DC bus voltage goes below a certain level E009 CT error If the V2000 built in current transformer is not functioning properly the inverter will...
Страница 48: ...ings have been selected and the inverter currently is in its initializing phase refer to functions b 84 and b 85 The parameters for the European market EU are loaded For non European inverter models t...
Страница 49: ...been selected Has the correct source for the running command A 02 been selected Correct the A 01 parameter setting if necessary Correct the A 02 parameter setting if necessary The motor won t start N...
Страница 50: ...ter the power supply was left in the on state for only less than 6 seconds Copy the parameter settings once more and then keep the power supply turned on for more than 6 seconds The motor won t start...
Страница 51: ...is shut off EEPROM Undervoltage protection A decrease of DC bus voltage may result in improper function of the control unit It may also cause motor heating and low torque The inverter is shut off when...