Speed: remote potentiometer input
For remote potentiometer speed input, when
AUTO
hasbeen pressed:
Connect a potentiometer (±5% tolerance recommended) between pins 12 and 15, with a resistor in series
on the Max side of the potentiometer. Typical potentiometer value is 1kΩ-5kΩ. The resistor value should
be 180R when a 1kΩ potentiometer is used; the resistor value should be 1kΩ when a 5kΩ potentiometer is
used.
Note: Theresistor value may have to beadjusted higher or lower to achieve thefullpump speed range.
Connectthepotentiometer wiper to pin 2.
Note: Setthe pump to analogue control. Do notapply a voltage or currentcontrolinputsignalatthe same
time. Performance willdepend on thetolerancesof componentsused.
Remote
potentiometer
Min
Min
Max
Max
Remote
potentiometer
m-120-en-02