Example
If using a 4-20mA sensor with a range of 0-10psi:
l
Set the 4mA to 0psi
l
Set the 20mA to 10psi
l
The Alarm Max was set at 8psi
l
The Warning Max was set at 7psi
l
The Warning Min was set at 3psi
l
The Alarm Min was set at 2psi
A
L
W
L
2psi
3psi
A
H
W
H
9psi
8psi
20mA
10psi
Current (A)
Pressure (psi)
4mA
0psi
An alarm event is indicated by the solid lines (A
L
, A
H
) on the graph. During an alarm event the pump will
show the alarm red screen and stop. This alarm is triggered by the sensor signal being equal to or
greater than that set by the Alarm Max/Min or Ethernet Hi-Hi/Lo-Lo Parameters. The user has to
acknowledge this screen on the pump.
A warning event is indicated by the dashed lines (W
L
, W
H
) on the graph. During a warning event the
pump will show orange sections on the screen and a warning bit will flag on the Ethernet
communications. This event is triggered by the sensor signal being equal to or greater than the value set
by the Warning Max/Min or Ethernet Hi-Lo/Lo-Hi Parameters.
Note:
It is normal to expect fluctuations in both pressure and flow systems using peristaltic pumps. This
means that warning and alarm limits need to take short term spikes and changes into account when
setting these limits.
Note:
The pump has no control over the accuracy of the signals coming from the sensors and will
simply respond to the signal levels received. Sensor accuracy is the responsibility of the sensor supplier
and will be dependent on a range of system variables, for example fluid type, tube material and
temperature.
82
m-530en-en-01
Содержание 530 Series
Страница 35: ...13 7 Network topology Star network Ring network m 530en en 01 35...
Страница 83: ...20 5 Flow Sensor Reading The flow sensor value can be read via the Flow sensor reading screen m 530en en 01 83...
Страница 104: ...22 Help 22 1 Help Select Help from the main menu to access the help screens 104 m 530en en 01...
Страница 127: ...32 Publication history m 530en 01 530 EN pump First published 04 2020 m 530en en 01 127...