background image

19.4

Setting up the PC

In the ‘Internet Protocol Version 4 (TCP/IPv4)
Properties’ window, select the ‘Use the following IP
address’ button and inputting the below network
settings. Press OK once done. This can be found in
the “Network Connections” window by right clicking
on the “Ethernet” connection and going to
properties .

Set as follows:

l

IP Address: 192.168.1.13

l

Subnet Mask: 255.255.255.0

l

Default Gateway: 192.168.1.1

Select ‘OK’ (outlined in red), then close all open windows.

m-530en-en-01

51

Содержание 530 Series

Страница 1: ...turning pumps 8 5 Peristaltic pumps an overview 8 6 Warranty 9 7 Safety notes 10 8 Pump specifications 13 8 1 Specification ratings 13 8 2 Weights 13 8 3 Pumphead options 14 9 Good pump installation p...

Страница 2: ...36 14 1 Selecting the display language 36 14 2 First time start up defaults 38 15 Switching the pump on in subsequent power cycles 39 16 Mode menu 40 17 Manual 41 17 1 START 41 17 2 STOP 42 17 3 INCR...

Страница 3: ...codes 105 23 2 Technical support 106 24 Drive maintenance 107 25 Drive spares 108 26 Pumphead replacement 109 26 1 Pumphead replacement 109 27 Tube replacement 110 27 1 Continuous tubing 110 27 2 Tub...

Страница 4: ...Original instructions The original instructions for this manual have been written in English Other language versions of this manual are a translation of the original instructions 4 m 530en en 01...

Страница 5: ...Machinery Directive 2006 42 EC EMC Directive 2014 30 EC ROHS Directive 2015 863 6 Harmonised standards used BS EN61010 1 2010 third edition Safety requirements for electrical equipment for measuremen...

Страница 6: ...uality Management System ISO 9001 and the technical documentation is compiled in accordance with Annex VII B of the Directive We undertake to transmit in response to a reasoned request by the appropri...

Страница 7: ...ents supplied 530 Components l 530 pump drive unit fitted with 520R2 or other pumphead if specified as a pump l The designated power cable attached to the pump drive unit l A 530N module providing pum...

Страница 8: ...er advances along the tube the seal also advances After the roller has passed the tube returns to its original shape creating a partial vacuum which is filled by fluid drawn from the inlet port Before...

Страница 9: ...warranty does not obligate Watson Marlow to bear any costs of removal installation transportation or other charges which may arise in connection with a warranty claim Watson Marlow shall not be respon...

Страница 10: ...regulations and guidance This symbol used on the pump and in the manual means An appropriate safety instruction should be followed or caution to a potential hazard exists This symbol used on the pump...

Страница 11: ...are no user serviceable fuses or parts inside this pump Note the mains power supply cable is supplied hardwired into the pump and is not customer replaceable Observe voltage selector switch setting f...

Страница 12: ...mical please contact Watson Marlow to confirm compatibility There are moving parts inside the pumphead Before opening the tool unlockable guard or tool unlockable track ensure that the following safet...

Страница 13: ...cable connections conforming to the best practice of noise immunity Full load current 530 0 6A 230V 1 25A 115V Fuse rating T2 5AH250V 5x20mm Installation category overvoltage category II Pollution de...

Страница 14: ...and Safety guidelines Finger recesses are built into the sides of the lower shell for convenience in lifting in addition the pump can conveniently be lifted by grasping the pumphead and where fitted...

Страница 15: ...suitable local emergency stop device is fitted into the mains supply to the pump Do not stack the pumps more than the recommended maximum number When the pumps are stacked ensure that the ambient tem...

Страница 16: ...s connected to the inlet and discharge port of the pumphead to help to minimise impulse losses and pulsation in the pipeline This is especially important with viscous fluids and when connecting to rig...

Страница 17: ...nown operating mode FUNCTION keys FUNCTION keys when pressed will perform the function displayed on the screen directly above the relevant function key and keys These keys are used to change the progr...

Страница 18: ...10 2 Starting and stopping 10 3 Using up and down keys 10 4 Maximum speed 10 5 Change rotation direction 18 m 530en en 01...

Страница 19: ...the switch plate at the rear of the pump protected from water by the N module The module must be removed to allow access to the switch plate Do not switch the pump on unless you have checked that it i...

Страница 20: ...NEMA 4X modules fitted to 530 630 and 730 En cased pumps have two pairs of wiring ports Two M16 ports are provided together with glands to seal circular cross section cables ranging in diameter from...

Страница 21: ...EtherNet IP specification for use in industrial automation systems using EtherNet IP 2 If there is a requirement to connect the M12 body and cable screen A to Mains earth for EMC or Ethernet TCP reas...

Страница 22: ...hat proper connections are achieved between the pump and suction and discharge piping o Ensure proper connection has been made to a suitable power supply o Ensure that the recommendations in the secti...

Страница 23: ...signals to the maximum values shown Do not apply voltage across other pins Permanent damage not covered by warranty may result Keep 4 20mA and low voltage signals separate from mains power Use separa...

Страница 24: ...sensor use Analogue input voltage mode VAin 15 10 30 V 0 10V range 100R source impedance Analogue input voltage mode RVA in 34 4 k 3 Analogue input measurement range Iin 0 25 mA Analogue input current...

Страница 25: ...5 6 8 7 2 1 1 RJ45 connection 1 2 RJ45 connection 2 3 Standard 9 way D Sensor connector Female 4 USB Type A port for service use only 5 Voltage selector switch 6 On Off switch 7 Mains power cable 8 C...

Страница 26: ...activity High Low One green LED on for link detected flickers to indicate 100 Mbit activity High High Two green LEDs on for link detected flickers to indicate 1Gbit activity 13 4 Sensor Wiring IP31 St...

Страница 27: ...ry no leak Clockwise rotation Manual keypad control Wet leak detected Anticlockwise rotation Analogue Wiring the D connector Signal Name Input or output Configurable Signal response 1 5 6 9 0V ANALOGU...

Страница 28: ...Signal Name Input or output Configurable Signal response 1 5 6 9 1KHz FREQ 0V 1 5 6 9 FREQ VAUX 200Hz Input Yes 1 5 6 9 LEAK VAUX VDC 0V 1 5 6 9 LEAK Input Yes 28 m 530en en 01...

Страница 29: ...Signal Name Input or output Configurable Signal response 1 5 6 9 STOP VAUX 1 5 6 9 VDC STOP 0V Input Yes m 530en en 01 29...

Страница 30: ...over is correctly secured at all times by all screws supplied Failure to do so may compromise the IP66 NEMA 4X protection Ensure that unused openings on the module are sealed using the blanking plugs...

Страница 31: ...r PCB 1 2 U1 1 Without isolated power supply option N Module 2 With isolated power supply option F Module Note Disconnect the adapter module by use of the ribbon eject levers It is recommended to leav...

Страница 32: ...etely separates the terminal 24V and 0V from the pump internal supplies This may be used if the sensor requires an isolated supply or has a 4 20mA output which cannot be used with the ground connected...

Страница 33: ...lockwise rotation Manual keypad control Wet leak detected Anticlockwise rotation Analogue Connector No Function Input or output Configurable Signal response J1 No Connection to pump J2 AN1 P ANALOGUE...

Страница 34: ...ut or output Configurable Signal response J4 SP LK STOP LEAK 22V SP LK STOP LEAK 22V VDC VDC Input Yes J5 PRESS 0VA PRESS FREQ FREQ VDC PRESS 0VA PRESS FREQ FREQ 22V 200Hz 1KHz Input Yes J6 1 Earth 2...

Страница 35: ...13 7 Network topology Star network Ring network m 530en en 01 35...

Страница 36: ...irst time Power up the pump The pump displays the start up screen with the Watson Marlow Pumps logo for three seconds 14 1 Selecting the display language 1 Use the keys to select your chosen language...

Страница 37: ...ge will now be displayed on screen Choose CONFIRM to continue All text will now appear in your chosen language 3 Choose REJECT to return to the language choice screen This then proceeds to the home sc...

Страница 38: ...its rpm SG value 1 Keypad lock Disabled Beeper ON Security code Not set Remote start stop input High stop Leak detector input High leak The pump is now ready to operate according to the defaults liste...

Страница 39: ...ched off last Check that the pump is set to operate as you require it The pump is now ready to operate All operating parameters may be changed by means of key presses see Pump operation on page 17 Pow...

Страница 40: ...play the Change mode menu Use the and keys to scroll through the available modes Manual default Flow calibration EtherNet IP CANCEL Use SELECT to choose mode Use the right hand function key to alter m...

Страница 41: ...to the last known settings from that operating mode when the power is re applied When the pump is running it displays an animated clockwise arrow In normal operation the direction of flow is into the...

Страница 42: ...y press will decrease flow rate by the least significant digit of the chosen flow rate unit o Repeat key presses as required to achieve the desired flow rate o Hold down the key for flow rate scrollin...

Страница 43: ...ON Manual mode only o Press and hold the MAX key to run at maximum flow o Release the key to stop the pump o The volume dispensed and time elapsed are displayed while the MAX key is pressed and held m...

Страница 44: ...n This pump displays flow rate in ml min 18 1 Setting the flow calibration Using the keys scroll to Flow calibration and press CALIBRATE Using the keys enter the maximum flow rate limit and press ENTE...

Страница 45: ...Press START to begin pumping a volume of fluid for calibration Press STOP to stop pumping fluid for the calibration m 530en en 01 45...

Страница 46: ...he keys to enter the actual volume of fluid pumped To accept the new calibration press ACCEPT or RE CALIBRATE to repeat the procedure Press HOME or MODE to abort The pump is now calibrated 46 m 530en...

Страница 47: ...of a static IP address Setting Value DHCP Enable Off IP Address 192 168 001 012 Subnet mask 255 255 255 000 Gateway address 192 168 001 001 1 Press the MODE key to access the MODE menu 2 Press the do...

Страница 48: ...ting the IP Address Subnet mask and Gateway address Configure each of the IP Address subnet mask and gateway address in turn using the following method 5 Use the UP and DOWN arrow keys to select the s...

Страница 49: ...d the UP or DOWN key increase the scrolling speed 8 Press NEXT to move to the next number 9 After setting the last number press CONFIRM to store the number and return to the ETHERNET IP SETTINGS scree...

Страница 50: ...etwork error as indicated above if the pump is not connected to a PC 19 3 Example for http connection between pump and PC peer to peer Refer to Configure EtherNet IP Settings on page 47 to set your pu...

Страница 51: ...ting the below network settings Press OK once done This can be found in the Network Connections window by right clicking on the Ethernet connection and going to properties Set as follows l IP Address...

Страница 52: ...tandard RJ45 network cable from the PC to the pump into either RJ45 connector 1 2 2 The Connected and Port 1 Connected or Port 2 Connected indicators will turn green followed by the IP Address The pum...

Страница 53: ...eb browser l Launch web browser e g Internet Explorer l Type 192 168 1 12 into the address bar The pump web page will open displaying the Overview tab 19 7 Connecting to a PLC This pump is designed in...

Страница 54: ...U32 19 PressureLo LoAlarmSp 24 U32 20 PressureHi HiAlarmSp 28 U32 21 FlowSensorLo HiWarningSp 32 U32 22 FlowSensorHi LoWarningSp 36 U32 23 FlowSensorLo LoAlarmSp 40 U32 24 FlowSensorHi HiAlarmSp 44 U...

Страница 55: ...72 U8 41 FlowSensorModel 73 U8 42 FlowSensorSize 74 U8 43 Reverse 75 U8 44 Running 76 BOOL 45 LeakDetected 77 BOOL 46 MotorStallError 78 BOOL 47 MotorSpeedError 79 BOOL 48 OverCurrentError 80 BOOL 49...

Страница 56: ...hernetIpMode 93 BOOL 62 EthernetIpActive 94 BOOL Assem150 O T Param No Signal Offset Type 1 SetFlowCal 0 U32 2 SetSpeed 4 U16 3 SetSpeedLimit 6 U16 4 SetFailsafeSpeed 8 U16 5 SetFailsafeEnable 10 U8 6...

Страница 57: ...DS Parameter Range Comments 1 SetFlowCal Write 15120 1 2147483647 Use to set the tube flow calibration value The flow calibration value is set in L For more information on flow calibration see Flow ca...

Страница 58: ...e 0 0 1 False True Set to 1 true to allow the pump to run 0 will stop the pump Note that pump enable needs to be set 8 RunEnable Write 0 0 1 False True Need to set to 1 to allow pump to run Setting to...

Страница 59: ...2147483647 2147483647 Reports a value if the flow sensor is setup 16 SensorPressure Read 0 2147483647 2147483647 Reports a value if the pressure sensor is setup 17 PressureLo HiWarningSp Read 1 0 214...

Страница 60: ...lution count in full rotations 27 PumpSpeed Read 100 1 2200 Displays the current pump speed set point in deci rpm 28 SpeedLimit Read 2200 1 2200 Displays the current speed limit set point in deci rpm...

Страница 61: ...the currently selected pump head See PumpHead on page 64 39 PressureSensorModel Read 0 0 3 Displays the currently selected pressure sensor model Please see PressureSensorModel enum table below 40 Pres...

Страница 62: ...se follow onscreen instructions 48 OverCurrentError Read 0 0 1 False True If set the pump has an over current error Please follow onscreen instructions 49 OverVoltageError Read 0 0 1 False True If set...

Страница 63: ...True If set the pressure high alarm is active 58 PressureLo HiActive Read 0 0 1 False True If set the pressure high warning is active 59 SensorErrorInput1 Read 0 0 1 False True If set there is an erro...

Страница 64: ...220rpm 5 520R 0 1 220rpm 6 520R2 0 1 220rpm 7 505L Continuous 0 1 220rpm 8 505L Double 0 1 220rpm 9 520 Sanitary 0 1 220rpm 10 520 Industrial 0 1 220rpm 11 620R 0 1 265rpm Default is 0 1 165rpm Max sp...

Страница 65: ...pm 16 620RE Industrial 0 1 265rpm 17 620RE4 Industrial 0 1 265rpm 18 720R 0 1 360rpm 19 720 Sanitary 0 1 360rpm 20 720 Industrial 0 1 360rpm Wallsize Enum Number WallSize Comments 0 0 8mm 1 1 6mm 2 2...

Страница 66: ...19mm 2 0 25mm 3 0 38mm 4 0 50mm 5 0 63mm 6 0 76mm 7 0 80mm 8 0 88mm 9 1 02mm 10 1 14mm 11 1 29mm 12 1 42mm 13 1 52mm 14 1 60mm 15 1 65mm 16 1 85mm 17 2 05mm 18 2 29mm 19 2 54mm 20 2 79mm 21 3 20mm 22...

Страница 67: ...32 25 4mm PressureSensorModel Enum Number Pressure Sensor Model Comments 0 None 1 Press N 0xx 2 Parker Scilog 3 Generic Pressure PressureSensorSize Enum Number Pressure Sensor Size Comments 0 None 1...

Страница 68: ...Sensor Model Comments 0 None 1 C0 55 V2 0 2 Em tec BioProTT 3 FlexMag 4050C 4 Generic Flow FlowSensorSize Enum Number Flow Sensor Size Comments 0 None 1 4050C_SIZE_38 2 4050C_SIZE_12 3 4050C_SIZE_34...

Страница 69: ...the user to configure warning and alarm set points on the pump Each pump can support a maximum of one flow sensor and one pressure sensor at the same time 20 1 Sensor wiring Make sure the sensor is c...

Страница 70: ...Setting up the sensors From the control settings menu using the keys scroll to Sensor settings option and press SELECT Using the keys scroll to Configure sensors option and press SELECT 70 m 530en en...

Страница 71: ...ress SELECT This selects the type of sensor to configure A list of supported flow sensor families are displayed The example in the image above shows supported flow sensors Using the keys scroll to the...

Страница 72: ...hed to needs to be assigned Using the keys scroll to the desired flow sensor and press SELECT See Control wiring section for connection specifications Using the keys scroll to the desired sensor size...

Страница 73: ...l to the desired output unit and press SELECT This choice will alter the units displayed on the home screen Set Alarm and Warning level Using the keys scroll to the alarm level to set up and press SEL...

Страница 74: ...press SELECT to store Each one of these defaults to none once the user sets a value in the edit screens the alarm warning will become active When a warning level is triggered the top or bottom bars w...

Страница 75: ...pump will stop 20 3 Start up delay Sets the delay from the motor starting to the alarms warnings activating Start up delay activates on a motor start irrelevant of mode includes MAX From the control s...

Страница 76: ...From the control settings menu using the keys scroll to set sensor delay option and press SELECT Using the keys set a value and press SELECT to store 76 m 530en en 01...

Страница 77: ...nse to be used on the system The sensor max flow pressure ratings are shown in a table at the end of this section From the control settings menu using the keys scroll to Sensor settings option and pre...

Страница 78: ...ys scroll to Flow or Pressure option and press SELECT This selects the type of sensor to configure Using the keys scroll to Generic flow sensor or Generic pressure sensor option and press SELECT 78 m...

Страница 79: ...ection the user has connected the sensor to See Control wiring section for connection specifications Only generic sensors which provide a 4 20mA output are supported Using the keys select the sensor u...

Страница 80: ...in l min After selecting the sensor unit type the user will progress onto the calibrate generic sensor screen Using the v keys change the value reported when the sensor input is at 4mA Once satisfied...

Страница 81: ...essure Unit Minimum Maximum PSI 10 0 75 Bar 0 689 5 171 Flow Unit Minimum Maximum ul min 0 60000000 ml min 0 60000 ml hr 0 900000 l min 0 60 l hr 0 900 The Warning error levels screen will then be sho...

Страница 82: ...ed by the dashed lines WL WH on the graph During a warning event the pump will show orange sections on the screen and a warning bit will flag on the Ethernet communications This event is triggered by...

Страница 83: ...20 5 Flow Sensor Reading The flow sensor value can be read via the Flow sensor reading screen m 530en en 01 83...

Страница 84: ...of the HOME screens or INFO screens This will display the main menu as shown below Use the keys to move the selection bar between the available options Press SELECT to choose an option Press EXIT to r...

Страница 85: ...e Main menu Auto keypad lock Press ENABLE DISABLE to switch on off the Auto keypad lock When active the keypad will lock after 20 seconds of inactivity Once locked it will display the screen below whe...

Страница 86: ...equired to disable PIN lock Setting Master PIN Setting the Master PIN protects all functionality The Master is able to selectively enable functionality for two additional operators These are defined a...

Страница 87: ...Now press CONFIRM to check that the number entered is the PIN you require Press CHANGE to return to PIN entry m 530en en 01 87...

Страница 88: ...tionality Press NEXT to selectively enable functionality access for User 1 and User 2 Configure User 1 security settings The PIN PROTECTION level screen will be displayed with User 1 highlighted press...

Страница 89: ...digit User 1 PIN use the keys to select each digit from 0 9 Once you have the required digit press the NEXT DIGIT key After selecting the fourth digit press ENTER Now press CONFIRM to verify that the...

Страница 90: ...isable functionality highlight the enabled functionality and press DISABLE When all the required functionality has been enabled press FINISH Configure User 2 security settings The PIN PROTECTION level...

Страница 91: ...ss the NEXT DIGIT key After selecting the fourth digit press ENTER To define the allowed functionality use the keys to select the functionality and press ENABLE User 2 PIN will allow access to only th...

Страница 92: ...ned functionality To enter the PIN use the keys to select each digit from 0 9 Once you have the required digit press the NEXT DIGIT key After selecting the fourth digit press ENTER If an incorrect PIN...

Страница 93: ...ot allow access to the functionality the following screen will be displayed Keypad beep From SECURITY settings scroll to Keypad beep using the keys and select ENABLE The pump will now beep at every ke...

Страница 94: ...me control screen Disabling this feature does not change any other aspects of PIN code operation Anyone wishing to modify pump settings will still need to enter the PIN code 21 2 General settings To v...

Страница 95: ...flow units move the selection bar over the flow unit menu entry and press SELECT Use the keys to move the selection bar over the required flow unit then press SELECT All flow rates displayed on screen...

Страница 96: ...nu entry and press SELECT If a pump label has been previously defined this will be displayed on screen to allow editing otherwise it will display the default label WATSON MARLOW Use the keys to scroll...

Страница 97: ...y and return to the general settings menu Pumphead type Select GENERAL SETTINGS from the main menu Use the keys to move the selection bar over Pumphead type and press SELECT The following screen will...

Страница 98: ...Use the keys to move the selection bar over Pumphead and press SELECT Use the keys to move the selection bar over the required pumphead type and press SELECT 98 m 530en en 01...

Страница 99: ...rial Select Tube size from GENERAL SETTINGS then use the keys to move the selection bar over Bore size and press SELECT Use the keys to move the selection bar over the tube size to be used and press S...

Страница 100: ...as been selected then the tube size is displayed as pressure and bore This screen also allows you to select the tube material used Use the keys to move the selection bar over Tube material and press S...

Страница 101: ...through the available characters for each digit The available characters are 0 9 A Z and SPACE Press NEXT to move onto the next character or PREVIOUS to move back to the last character Press FINISH t...

Страница 102: ...ative display language for the pump The pump must be stopped before changing the language Use the keys to move the selection bar to your required language Press SELECT to confirm Your selected languag...

Страница 103: ...MODE key Please see Mode menu on page 1 for further details Reset run hours Select Reset run hours from the control settings menu Select RESET to zero the run hours counter The run hours counter can b...

Страница 104: ...22 Help 22 1 Help Select Help from the main menu to access the help screens 104 m 530en en 01...

Страница 105: ...t or burst Check that the correct wall thickness tube is being used Check the direction of rotation Check that the rotor is not slipping on the drive shaft If the pump turns on but will not run Check...

Страница 106: ...ump immediately Power OFF ON may reset Or seek support Er16 Over voltage Stop pump immediately Check supply Power OFF ON may reset Er17 Under voltage Stop pump immediately Check supply Power OFF ON ma...

Страница 107: ...24 Drive maintenance There are no user serviceable parts inside the pump Please contact your local Watson Marlow representative to arrange repair m 530en en 01 107...

Страница 108: ...M12 collars insulated MN2934T M12 collars non insulated MN2935T Ethernet Cable M12D Right Angle 4 pin plug to M12D Straight 4 pin plug CAT 5 SHIELDED 3m 059 9121 000 Ethernet Cable M12D Right Angle 4...

Страница 109: ...cement Always isolate the pump from the mains power supply before opening any guard or track or performing any positioning removal or maintenance operation 26 1 Pumphead replacement 520R 1 2 3 4 5 6 m...

Страница 110: ...p from the mains power supply before opening any guard or track or performing any positioning removal or maintenance operation 27 1 Continuous tubing 520R and 520R2 1 2 3 4 5 6 7 8 9 505L 1 2 3 4 5 6...

Страница 111: ...27 2 Tube elements Grey Beige Blue 2 bar 30psi 4 bar 60psi 7 bar 100psi 520REL 520REM and 520REH 1 2 3 4 5 530 Sanitary connectors 1 2 3 530 Industrial connectors 1 2 3 m 530en en 01 111...

Страница 112: ...t exposure to less than one minute risk of attack Halogenated chlorinated solvents Not recommended possible risk to polycarbonate tube clamp adjusters and polypropylene tube clamp locators Alcohols ge...

Страница 113: ...ins plug A American mains plug K Australia mains plug R Argentina mains plug C Swiss mains plug D India South Africa mains plug B Brazilian mains plug For non profibus and EtherNet IP pumps this optio...

Страница 114: ...933 0048 016 966 0048 016 6 4 1 4 17 902 0064 016 933 0064 016 966 0064 016 8 0 5 16 18 902 0080 016 933 0080 016 966 0080 016 mm inch STA PURE Series PCS Neoprene 0 8 1 32 13 920 0008 016 1 6 1 16 14...

Страница 115: ...8 3 16 15 902 0048 024 933 0048 024 913 A048 024 6 4 1 4 24 902 0064 024 933 0064 024 913 A064 024 8 0 5 16 121 902 0080 024 933 0080 024 913 A080 024 9 6 3 8 122 902 0096 024 933 0096 024 913 A096 0...

Страница 116: ...e TL Pumpsil STA PURE Series PCS STA PURE Series PFL 3 2 1 8 16 933 0032 PFT 913 A032 PFT 961 0032 PFT 966 0032 PFT 6 4 1 4 17 933 0064 PFT 913 A064 PFT 961 0064 PFT 966 0064 PFT 9 6 3 8 122 933 0096...

Страница 117: ...7 bar 60 100 psi pressure rated elements Industrial mm inch Marprene TH 3 2 1 8 16 902 H032 PFQ Sanitary mm inch Bioprene TH STA PURE Series PCS 3 2 1 8 16 933 H032 PFT 961 H032 PFT m 530en en 01 117...

Страница 118: ...MNA2050A 520R 520R2 Pumphead guard complete with tool unlockable latch 2 MNA2045A 520R 520R2 Track assembly for cased pumps complete with spring loaded tube clamps 3 MNA2043A 520R 1 6mm wall tube Roto...

Страница 119: ...520RE 5 MNA2005A 520R 520R2 Top RH tube clamp MN2002M 520R 520R2 Tube clamp location plug 6 MN2034B Guard latch spring MN2005M Guard latch spring cartridge 7 MNA2147A 520RE Pumphead guard complete wi...

Страница 120: ...and discharge pressures for the pumphead at different drive speeds This data was produced pumping water at ambient temperature Marprene continuous tubing 1 6mm wall 200rpm clockwise rotation 8 0mm 6...

Страница 121: ...ll 200rpm counter clockwise rotation 1 6mm suction bar pressure bar 3 2mm 4 8mm 6 4mm 8 0mm Marprene continuous tubing 2 4mm wall 200rpm clockwise rotation 9 6mm 8 0mm 6 4mm 4 8mm 3 2mm 1 6mm suction...

Страница 122: ...wall 200rpm counter clockwise rotation 9 6mm 8 0mm 6 4mm 4 8mm 3 2mm 1 6mm suction bar pressure bar Marprene TL element 0 2 bar 0 30psi 200rpm counter clockwise rotation Suction bar Pressure bar 9 6m...

Страница 123: ...2 bar 0 30psi 200rpm counter clockwise rotation 9 6mm 6 4mm 3 2mm Suction bar Pressure bar Marprene TM element 2 4 bar 20 60psi 200rpm counter clockwise rotation Suction bar Pressure bar 6 4mm 3 2mm...

Страница 124: ...ent 2 4 bar 30 60psi 200rpm counter clockwise rotation 6 4mm 3 2mm Suction bar Pressure bar Marprene TH element 4 7 bar 60 100psi 200rpm counter clockwise rotation Suction bar Pressure bar 3 2mm 124 m...

Страница 125: ...e registered trademarks of Watson Marlow Limited Tri Clamp is a registered trademark of Alfa Laval Corporate AB STA PURE Series PCS and STA PURE Series PFL are trademarks of W L Gore and Associates Et...

Страница 126: ...rect but Watson Marlow Fluid Technology Group accepts no liability for any errors it contains and reserves the right to alter specifications without notice WARNING This product is not designed for use...

Страница 127: ...32 Publication history m 530en 01 530 EN pump First published 04 2020 m 530en en 01 127...

Отзывы: