Document #10-32813 Rev A; June 07, 2019
Page
41
of 69
Key
Value
Feature
Definition
Discover 0 = dis-
abled
1 =
enabled
intermodule bus
over Ethernet dis-
covery
This key is enabled by default. It enables or disables the intermodule bus over Eth-
ernet discovery feature. When discovery is disabled (the value is set to 0), software
tools will not discover the device.
This record is not in the setup.csv file by default. To use this feature, add this key and
value to the setup.csv file.
Setup Key: Discover
Ethernet 70 (0x46), Instance 2
Member ID Member Name Data Type Access NV Min Max Default Comments / Description
7
0x07 Watbus Enable
ENUM16
RW
F
--
--
-- 106
59: No
106: Yes
Modbus
®
TCP Server
Key
Value
Feature Definition
ModbusTCP nor:\Gateway\ModbusTcp.csv
Modbus®
TCP
Server
Full file name / path where the Modbus® TCP field bus gateway file
lives. This file associates Modbus® TCP registers with data points
from any of the four local busses.
Setup Key: Modbus® TCP
The RMA PLUS is a Modbus® TCP server and provides up to three (priority based) Modbus® TCP sessions. This ser-
vice is enabled by default for all model numbers. It may be disabled by writing “No” to the Modbus® TCP Enable mem-
ber. NOTE: A reset is required for this change to take effect.
Modbus® TCP does not proxy requests and there is virtually no delay between request and response. A keep-alive fea-
ture is enabled on all accepted sockets to prevent leaks if a socket is not closed properly after an applicationcrash, loss
of link, severed network, half-close, etc.
The RMA PLUS implements the following Modbus® function codes:
l
3: Read Holding Registers
l
4: Read Input Registers
l
6: Write Single Register
l
16: Write Multiple Registers
Modbus® TCP supports all integer data types, floats, enums, and parameter types, but not strings.
The 16-bit word / register order of multi-register data types may be changed. By default, the word order is low, high.
Member
ID
Member Name
Data
Type
Access
NV Min
Max
Default
Comments
3
0x03 Modbus® TCP Enable
ENUM16
RW
F
106
59: no; 106: yes
4
0x04
Modbus® TCP Word
Order
ENUM16
RW
F
1331
1331: Low High; 1330: High
Low
The object model for the Modbus® TCP server is user-defined. A sample file (shown below) exists in the path defined by
the key ModbusTCP. Add records to this file as necessary keeping the following in mind: