PM3/PM6 LEGACY™ Express PID Controller • 23 •
Setup Menu
‰
[`loC]
Lockout Menu
[`SEn]
Sensor Type
[`Lin]
Linearization
[`deC]
Decimal
[`C_F]
Display Units
[`r;lo]
Range Low
[`r;hi]
Range High
[`fn1]
Function Output 1
[`o;ty]
Output Type
[`fn2]
Function Output 2
[`h;ag]
Heat Algorithm
[`h;sC]
Hysteresis (Heat & Cool)
[`C;Ag]
Cool Algorithm
[`A;ty]
Alarm Type
[`A;hy]
Alarm Hysteresis
[`A;lg]
Alarm Logic
[`A;lA]
Alarm Latching
[`A;bl]
Alarm Blocking
[`A;si]
Alarm Silencing
[A;dsp]
Alarm Display
[``rp]
Ramp Action
[`r;rt]
Ramp Rate
[`s;lo]
Scale Low
[`s;hi]
Scale High
[o;hi1]
Power Scale High Output 1
[o;hi2]
Power Scale High Output 2
[`Ad;s]
Zone Address
[btth]
Bluetooth
SET UP MENU (Continued)
To enter the Setup Menu push and hold the
up and down arrow keys for approximately 3
seconds. Push the green advance key to scroll
through to the prompt of choice. Use the up
and down arrow keys to change the range.
Setup Menu (cont.)
Display
Parameter Name Description
[`fn2]
[ fn2]
Function of Output 2
Select which function will drive this
output.
Appears if: If output 2 is ordered
Range (Defaults are shown in bold)
[`oFF]
Off,
[CooL]
Cool,
[hEAt]
Heat,
[ALM]
Alarm
[`h;Ag]
[ h.Ag]
Heat Algorithm
Set the heat control method.
Appears if: Output 1 or 2 set to heat
Range (Defaults are shown in bold)
[`oFF]
Off,
[`Pid]
PID
[on;of]
On-Off
[`hSC]
[ hSC]
Hysteresis (Heat & Cool)
Set the control switching hysteresis for
on-off control. This determines how
far into the “on” region the process
value needs to move before the output
turns on.
Appears if: Heat or Cool Algorithm is
set to On-Off.
Range (Defaults are shown in bold)
0
to 9,999.000°F or units
0 to 5,555.000°C
Units, 3.0°F or 2.0°C
[`C;Ag]
[ C.Ag]
Cool Algorithm
Set the cool control method.
Appears if: If Output 1 or 2 is set
to cool
Range (Defaults are shown in bold)
[`oFF]
Off,
[
`Pid]
PID
[on;of]
On-Off
[`A;ty]
[ A.ty]
Alarm Type
Selects whether the Alarm will be a
Process Alarm/Absolute Tempera-
ture; or a Deviation Alarm/Tempera-
ture with respect to Setpoint.
Appears if: Always
Range (Defaults are shown in bold)
[`oFF]
Off,
[PR;AL]
Process Alarm
[dE;AL]
Deviation Alarm
Setup Menu