PM3/PM6 LEGACY™ Express PID Controller • 19 •
Operations Menu
‰
[````]
PAr1
[````]
PAr2
[`AUt]
Autotune
[`C;M]
Control Mode
[`h;pb]
Heat Proportional Band
[`C;pb]
Cool Proportional Band
[``ti]
Time Integral
[``td]
Time Derivative
[o;tb1]
Time Base
[o;tb2]
Time Base
[`A;lo]
Alarm Low Set Point
[`A;hi]
Alarm High Set Point
[`i;Ca]
Calibration Offset
[btth]
Bluetooth
Operations Menu
OPERATION MENU (Continued)
Upon power up of the control, using the
advance key will scroll through the various
prompts found in the Operations Menu.
At any point within the Operations menu
to return to the default display push the
Infinity ˆ key.
[``ti]
[ ti]
Time Integral
Set the PID integral for the outputs.
Appears if: Heat or cool algorithm
set to PID
Range (Defaults are shown in bold)
0 to 9,999 seconds per repeat
180
[``td]
[ td]
Time Derivative
Set the PID derivative time for the
outputs.
Appears if: Heat or cool algorithm
set to PID
Range (Defaults are shown in bold)
0 to 9,999 seconds
0 seconds
[o;tb1]
[o.tb1]
Time Base Output 1
Set the time base for fixed-time-base
control.
Appears if: Output 1 set to heat or
cool with control algorithm set to PID.
Range (Defaults are shown in bold)
0.1 to 60.0 seconds (solid-state relay
or switched dc)
5.0 to 60.0 seconds (mechanical relay
& NO-ARC power control)
1 sec. [SSR & sw dc], 20.0 sec.
[mech. relay & NO-ARC]
[o;tb2]
[o.tb2]
Time Base Output 2
Set the time base for fixed-time-base
control.
Appears if: Output 2 set to heat or
cool with control algorithm set to PID.
Range (Defaults are shown in bold)
0.1 to 60.0 seconds (solid-state relay
or switched dc)
5.0 to 60.0 seconds (mechanical relay
& NO-ARC power control)
1 sec. [SSR & sw dc], 20.0 sec.
[mech. relay & NO-ARC]