PM3/PM6 LEGACY™ Express PID Controller • 20 •
Setup Menu
[`A;Lo]
[ A.Lo]
Alarm Low Set Point
Process - set the process value that
will trigger a low alarm.
Deviation - set the span of units
(Must be negative number) from the
closed loop set point that will trig-
ger a low alarm.
Appears if: If Alarm Type [`A;ty] is set
to Process or Deviation Alarm
Range (Defaults are shown in bold)
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 32.0°F or 0.0°C
[`A;hi]
[ A.hi]
Alarm High Set Point
Process - set the process value that
will trigger a high alarm.
Deviation - set the span of units from
the closed loop set point that will
trigger a high alarm.
Appears if: If Alarm Type (A.ty) is set
to Process or Deviation Alarm
Range (Defaults are shown in bold)
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 300.0°F or 150.0°C
[`i;CA]
[ i.CA]
Calibration Offset
Set an offset value for a process
output.
Appears if: Always
Range (Defaults are shown in bold)
[
-1,999.000 to 9,999.000°F or units,
-1,110.555 to 5,555.000°C,
0.0
OPERATION MENU (Continued)
Upon power up of the control, using the
advance key will scroll through the various
prompts found in the Operations Menu. At any
point within the Operations menu to return to
the default display push the Infinity ˆ key.
[````]
PAr1
[````]
PAr2
[`AUt]
Autotune
[`C;M]
Control Mode
[`h;pb]
Heat Proportional Band
[`C;pb]
Cool Proportional Band
[``ti]
Time Integral
[``td]
Time Derivative
[o;tb1]
Time Base
[o;tb2]
Time Base
[`A;lo]
Alarm Low Set Point
[`A;hi]
Alarm High Set Point
[`i;Ca]
Calibration Offset
‰
Operations Menu