Watlow Series 935A User’s Manual
5 7
PID Menu
Prompt
Range
Default
Hidden if *
Your Settings
[`tA9]
=
[P```]
;
or if
[Pb`c]
≠
0
3°F or 2°C
[```1] [`999]
[```1] [`555]
[``)1] [99(0]
[``)1] [55%0]
Select a value in whole
degrees (1°F to 999°F or
1°C to 555°C) or in
tenths of degrees (0.1°F
to 999.0°F or 0.1°C to
555.0°C).
[hYSc]
Hysteresis Cool
[`tA9]
=
[P```]
;
or if
[`Ot1]
≠
[cool]
and/or
[`Ot2]
≠
[cool]
25°F or 17°C
[```0] [`999]
[```0] [`555]
[``)0] [99(0]
[``)0] [55%0]
Select a value in whole
degrees (0°F to 999°F or
0°C to 555°C) or in
tenths of degrees (0.0°F
to 999.0°F or 0.0°C to
555.0°C).
[Pb`c]
Proportional Band Cool
[`tA9]
=
[P```]
;
or if
[`Ot1]
=
[cool]
and
[`Ot2]
≠
[hEAt]
;
or if
[`Ot1]
=
[hEAt]
and
[`Ot2]
≠
[cool]
0°F or 0°C
[```0] [`999]
[```0] [`555]
[``)0] [99(0]
[``)0] [55%0]
Select a value in whole
degrees (0°F to 999°F or
0°C to 555°C) or in
tenths of degrees (0.0°F
to 999.0°F or 0.0°C to
555.0°C).
[``db]
Dead Band
[`tA9]
=
[P```]
;
or if
[Pb`h]
= 0
1.0 second
[``)1] [`6)0]
[``%0] [`6)0]
Select a value between
0.1 and 60.0 seconds
(Solid-State Relay or
Switched DC) or 5.0 and
60.0 seconds
(Electromechanical
Relay).
[Ct`h]
Cycle Time Heat
Содержание 935A Series
Страница 55: ...Watlow Series 935A User s Manual 53 Notes...
Страница 56: ...54 Watlow Series 935A User s Manual Notes...
Страница 65: ...Watlow Series 935A User s Manual 63 Notes...
Страница 66: ...64 Watlow Series 935A User s Manual Notes...