![WaterLogic WL 1000 GF Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/waterlogic/wl-1000-gf/wl-1000-gf_technical-manual_875133010.webp)
18
19
Waterlogic 1000 GF Technical Manual - Issue A, July 2011
Installation Procedure
IMPORTANT NOTICE
This procedure should only be carried out by a technician trained by waterlogic
international or by an approved distributing agent.
Note: this appliance is intended for indoor use only. Cleaning of waterlogic prod-
ucts should not be carried out using a jet washer.
1.
Remove the 1000 GF from the packing box and inspect the unit for transit
damage.
2.
Mount the WL 1000 GF on a firm flat surface so that it cannot topple or fall over.
Ensure there is an air gap around the machine to allow the refrigeration circuit to
function correctly.
3.
It is advisable that the water and electricity supply are within two meters of the
WL 1000 GF and that the water isolation valve and power supply are accessible.
The WL 1000 GF should not be installed using an extension lead. The water sup-
ply should be from a potable source.
4.
Open the top cover by removing the screws at the rear and lift the top cover off
from the rear.
5.
Remove the lower front panel. The lower front panel is secured in place by two
locking screws on the left and right side of the panel and two locking clips under
the front lower panel.
6.
Inspect the water connection and the electrical connections in case they have
become loose in transit.
7.
Connect the water supply. All water sources should be potable. Allow the wa-
ter supply to run clear of any sediment before connecting to the WL 1000 GF. The
minimum pressure for the WL 1000 GF to function correctly is 22.5 PSI (1.5 bar).
The ideal pressure is 45 PSI. The maximum pressure is 60 PSI.
8.
Check the electrical wall socket (polarity) and then make the electrical connec-
tion to the WL 1000 GF by plugging the power lead in to the socket on the rear of
the WL 1000 GF. Then connect to the electrical feed wall power outlet and turn on
the power supply to the WL 1000 GF.
9.
The WL 1000 GF will start to automatically fill with water (please note carbon
filters should be pre-flushed before commissioning the WL 1000 GF so that exces-
sive carbon fines do not get into the WL 1000 GF RO membrane, tanks and sole-
noids). Back flush the RO membrane to waste for 10 litres to clean the membrane.
After back flushing the RO membrane and the WL 1000 GF stops filling, flush 10
litres of water through the WL 1000 GF by depressing the cold, ambient and hot
buttons. Turn on the green heater and compressor switches (rear) and the WL
1000 GF will start to heat and cool.
10.
The water temperature of the WL 1000 GF is factory set at 5°C for still cold wa-
ter and 85°C for hot water. The cold water temperature can be adjusted – the hot
water is non-adjustable.
11.
Carry out a visual inspection for any water leaks.
12.
Replace any covers and now test the water for taste. Any hint of plastic taste in
the water means the WL 1000 GF needs to be flushed with an additional 10 litres
of water.
13.
The WL 1000 GF should be sanitised at installation (see instructions).
14.
The WL 1000 GF must not be installed in direct sunlight, adjacent to a heat
source, or in an ambient room temperature above 30°C or below 5°C.