23

PREMIER 2 SINGLE-SPEED INSTALLATION AND MAINTENANCE MANUAL

WATER COIL MAINTENANCE

1)

Keep all air out of the water. An open loop system should be checked to ensure that the well

head is not allowing air to infiltrate the water line. Lines should always be airtight.

2)

Keep the system under pressure at all times. It is recommended in open loop systems that

the water control valve be placed in the discharge line to prevent loss of pressure during off

cycles. Closed loop systems must have positive static pressure.

NOTE: On open loop systems, if the installation is in an area with a known high mineral

content (125 ppm or greater) in the water, it is best to establish with the owner a periodic

maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be

necessary, use standard coil cleaning procedures which are compatible with either the cupro-

nickel or copper water lines. Generally, the more water flowing through the unit the less chance

for scaling.

OTHER MAINTENANCE

Filters

Filters must be clean to obtain maximum performance. They should be inspected monthly

under normal operating conditions and be replaced when necessary. Units should never be

operated without a filter.

Condensate Drain

In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to

treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, espe-

cially with dirty filters. Inspect twice a year to avoid the possibility of overflow.

Air Coil

The air coil must be cleaned to obtain maximum performance. Check once a year under

normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to

damage the aluminum fins while cleaning.

CAUTION: Fin edges are sharp.

NOTE: 

To obtain maximum performance, the air coil should be cleaned before start-up.  A 10

percent  solution of dishwasher detergent and water is recommended for both sides of coil; a
thorough water rinse should follow.

ECM2 Fan Motors

ECM2 Blower Motors are equipped with sealed ball bearings and require no periodic oiling.

Desuperheater Coils

See Water Coil Maintenance section above.

Preventative
Maintenance

Содержание AT019D

Страница 1: ...s received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received Examine units for shipping damage removing the units from the cartons i...

Страница 2: ...ll allow the control box to be removed with only the two front mounting screws for future service SETTING HORIZONTAL UNITS CAUTION Do not use rods smaller than 3 8 diameter since they may not be stron...

Страница 3: ...loosen a single nut The unit should be pitched approximately 1 4 towards the drain in both directions to facilitate the removal of condensate see Figure 5A on page 5 Use only the bolts provided in th...

Страница 4: ...ead the female locking ring onto the pipe threads while maintaining the brass connector in the desired direction see Figure 4B Tighten the connectors by hand then gently snug the fitting with pliers t...

Страница 5: ...ratures may be subject to freezing The water loop is usually maintained between 60 F and 90 F Premier 2 units allow 25 F 110 F EWT for proper heating and cooling operation This is accomplished with a...

Страница 6: ...age 7 final purging and charging of the loop is required A WaterFurnace flush cart or a 1 5 HP pump minimum is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from...

Страница 7: ...the motor housing has been flooded Ensure that the loop flow center provides adequate flow through the unit by checking the pressure drop across the heat exchanger and comparing it to the figures sho...

Страница 8: ...ne Premier AT or Spectra unit with optional circut board SL1 In SL1 Out Not Used Not Used Shut Down C C Premier 2 Unit 1 With pump wired to Unit 1 With pump wired to Unit 2 SL1 In SL1 Out Not Used Not...

Страница 9: ...lies of more than four use an 80 gallon water heater or two 50 gallon water heaters con nected in a series as shown in Figure 13 Electric water heaters are recommended Steps 1 Turn off the power to th...

Страница 10: ...temperature setting on the tank On tanks with both upper and lower elements the lower element should be turned down to the lowest setting approximately 100 F The upper element should be adjusted to 12...

Страница 11: ...complished by using the DHW pump disable switch located on the front of the unit cabinet near the LED annunciator panel The red DHW OFF LED will illuminate indicating the DHW pump is disabled Do not r...

Страница 12: ...and 3 of P3 See the wiring schematic on pages 13 16 for details 208 VOLT OPERATION All 208 230 volt units are factory wired for 230 volt operation For 208 volt operation the red and blue transformer...

Страница 13: ...m Norm Fan Comp Loop Well Test Norm Outputs Norm Inputs Norm 2 Speed 1 Speed ECM2 Air Flow Settings Field Selection Factory Setup NO NC CR3 COM Wh Blk Red F1 10A 240V Black Compressor CC T2 T1 Cap R S...

Страница 14: ...switch Legend Relay contacts N O N C Notes L1 L2 Single Disconnect Power 208 230 60 1 Aux Elect Power 208 230 60 1 L1 L2 L1 L2 AT Unit Power 208 230 60 1 CSA installed units only Local codes may requ...

Страница 15: ...P Thermistor Loop 15 F well 30 F Lockout High Pressure 380 PSI Lockout Low Pressure 15 PSI Lockout ECM2 RPM 100 rpm Lockout Microprocessor Malfunction HWL Thermistor 130 F DHW Pump Switch Off Drain Wa...

Страница 16: ...enable switch Thermal limit switch Legend Relay Contacts N O N C G T 1 3 2 P L1 PSC Fan Speed Relay PSC Fan Power Relay ER1 to ER4 Aux heat stage relays HWL Hot water limit sensor Premier2 Logic Board...

Страница 17: ...to medium speed 15 seconds after Y1 input The hot water pump is cycled 30 seconds after the Y1 input Heating 2nd Stage Y1 Y2 The hot water pump is de energized which directs all heat to satisfying the...

Страница 18: ...ly closed switch is opened for 30 continuous seconds Freeze Protection Water Flow This lockout mode occurs when the freeze thermistor temperature located between the TXV and coax is at or below the se...

Страница 19: ...r 24 VAC thermostats FACTORY SETUP DIP SWITCHES SW3 A 5 position DIP switch package on the Premier 2 control allows the following factory setup options 1 Two Speed Single Speed This DIP switch configu...

Страница 20: ......

Страница 21: ......

Страница 22: ...1 1 1 1 019 4 0 2 1 2 0 2 0 1 9 1 8 5 0 3 5 3 3 3 2 3 1 3 0 3 0 1 5 1 4 1 3 1 3 1 3 022 4 5 3 2 3 1 3 0 2 9 2 8 6 0 6 0 5 8 5 6 5 4 5 2 4 0 1 2 1 2 1 1 1 1 1 1 028 5 5 2 1 2 0 2 0 1 9 1 8 7 0 3 2 3 1...

Страница 23: ...scaling OTHER MAINTENANCE Filters Filters must be clean to obtain maximum performance They should be inspected monthly under normal operating conditions and be replaced when necessary Units should ne...

Страница 24: ...ir and water flow rates are at proper levels before servicing the refrigerant circuit To maintain sealed circuit integrity do not install service gauges unless unit operation appears abnormal refer to...

Страница 25: ...measurement with 2 voltage drop Wire size based on 60 C copper conductor With optional 1 hp ECM2 fan motor 208 230 60 3 All units rated 208 230 min 197 volt three phase 60 cycle All fuses type D time...

Страница 26: ...26 PREMIER 2 SINGLE SPEED INSTALLATION AND MAINTENANCE MANUAL Notes...

Страница 27: ...27 PREMIER 2 SINGLE SPEED INSTALLATION AND MAINTENANCE MANUAL...

Страница 28: ...ions without notice WaterFurnace and Premier are registered trademarks of WaterFurnace International Inc 1999 WaterFurnace International Inc Single Speed Installation and Maintenance Manual 9000 Conse...

Отзывы: