7.
The chimney system shall comply with the
standard for Chimney’s Factory-Built
Residential Type and Building Heating
Appliances UL 103.
8.
Any openings in a chimney guard if used
must not permit the entrance of a 3/4”
(19mm) diameter rod.
9.
CAUTION: THE STRUCTURAL INTEGRI
TY OF THE MOBILE HOME ROOF,
FLOOR, WALLS AND CEILING MUST BE
MAINTAINED.
10.
Check any other local building code as other
local codes may apply.
11.
WARNING: DO NOT INSTALL IN A
SLEEPING ROOM
WALL PROTECTORS
Materials and products listed for the purpose of
reducing clearance to combustibles shall be
installed in accordance with the conditions of the
listing and the clearances may be reduced by the
percentage reduction as stated in the wall shield
manufacturer’s instructions.
For clearance reduction systems using an air space
between the combustible wall and the wall protector,
adequate air circulation shall be provided by one of
the following methods.
1.
Adequate air circulation may be provided by
leaving all edges of the wall protector open
with at least a 1” 25mm air gap.
2.
If the wall protector is mounted on a single
flat wall away from corners, adequate air cir-
culation may be provided by leaving bottom
and top edges open with at least a 1” 25mm
air gap.
3.
Wall protectors that cover two walls in a cor-
ner shall be open at the bottom and top
edges with at least a 1” 25mm air gap.
5
Note:
Listed factory built chimney connectors
including elbows are acceptable for use in Mobile
Home Installation’s.