Service Analyser Codes (All Models) 

 

Most  problems  will  be  detected  by  the  electronic  control  and  a  code  will  appear  on  the 
temperature  display.    Make  sure  you  follow  the 

Action  /  Remedy

  instructions  where 

possible,  before  making  a  service  call  request  and  avoid  paying  unnecessary  service  call 
fees.    If  the  code  remains  on  the  display  after  you  have  followed  the 

Action  /  Remedy

 

instructions, please contact Waterco. 

 

Pool Heat Pump

 

| Pg 26

 

 

 

Service Analyser Codes 

Problem - Action / Remedy

 

 
Problem

:  Normal  defrost  cycle.  The  fan  blades  are  turning,  but  the 

compressor  has  stopped.    For  Ultra  and  Reversible  (XLR)  model,  the  fan 
blades do not turn but the compressor runs. 
 

Action / Remedy

: Normal during defrost cycle. 

Atmospheric conditions as well as the pool water temperature should not be 
below  the  minimum  operating  temperatures,  as  stated  below,  in  order  to 
obtain  efficiency  and  avoid  codes  from  appearing  on  the  electronic  control 
temperature display.  These codes are not generally a problem with the pool 
heat pump at these conditions and are not covered under warranty. 
 
If  temperatures  are  below  the  minimum  temperatures  the  pool  heat  pump 
should not be operated and must be switched off. 
 
For  Ultra  and  Reversible  (XLR)  units,  they  will  automatically  stop  without 
human intervention. 

 

Code 

 

DEF 

Problem - Action / Remedy

 

Code 

 

oC2, Sc2 

 
 
 
 

nFL 

 

Problem

: The intake temperature probe has a loose connection or is faulty. 

The probe will need to be checked and replaced, if required. 

 
Action / Remedy

: Contact customer service. 

 
Problem

: No water flow, not sufficient water flow through the pool heat pump 

or  the  water  pressure  switch  needs  to  be  adjusted  (not  covered  by  the 
warranty) or is defective. 
 

Action  /  Remedy

:  If  the  pool  pump  is  connected  to  the  pool  heat  pump, 

make sure the electronic control that runs the pool pump and pool heat pump 
are programmed correctly. 
 

If the code is still displayed: 

-

 

Make sure the pool pump is switched 

ON

-

 

Press 

ON/OFF

 to restart the pool heat pump; 

-

 

On new installations, ensure the installation instructions were respected; 

-

 

Check that the pool water level is correct, that the pool pump is filled with 
water to the rim and that water is flowing correctly through the pool pump 
to the pool heat pump; 

-

 

Check  swimming  pool  and  pool  pump  skimmer  baskets  and  the  drain  at 
the bottom of the pool for obstructions; 

-

 

Check  the  filter  cartridges  for  obstructions  (wash  or  change  the 
cartridges); 

-

 

Carry  out  a  backwash  for  sand  filters  and  ensure  they  are  working 
correctly; 

-

 

Ensure  that  the  bypass  valves  are  in  the  correct  positions  so  that  the 
water flows adequately; 

-

 

Ensure vacuum robot or other cleaners are disconnected so that the water 
flows freely; 

-

 

Check that there are no leaks on the pool plumbing (there should be no air 
leaks in the pipe work); 

-

 

If  you  have  a  two  speeds  pool  pump,  make  sure  it  is  set  at  the  highest 
speed. 

 
 

50 °F (10 °C) 

65 °F (18 °C) 

65 °F (18 °C) 

Pool water

 

temperature

 

must be above

 

Atmospherics conditions

 

must be above

 

Model

 

32 °F (0 °C) 

43 °F (6 °C) 

52 °F (11 °C) 

Ultra 

Reversible (XLR) 

All others 

 
 
 
For  Ultra  or  Reversible  (XLR)  Model:  If  the  unit  performs  4  consecutive 
cycles (heating and defrost) within 1 hour, the unit goes into protection mode 
and alternately displays the water temperature and the 

DEF

 code.  The fan 

motor  runs  for  30  minutes  to  cool  the  evaporator  and  then  stops.    The 
compressor is  always  off.    The unit  restarts  automatically  when  the  outside 
temperature is 43 °F (6 °C) and more. 
 

If the code stays on permanently

 

-

 

Ensure  the  evaporator  is  clean. 

If  not,  switch  the  unit  OFF  from  the 

circuit  breaker

  (fuse)  and  use  a  garden  hose  to  lightly  clean  the 

evaporator.  Allow it to dry before re-starting the pool heat pump to avoid 
premature ice build up on the evaporator. 

-

 

Ensure installation instructions have been followed.  Improper installation, 
e.g. no air circulation, could lead to the pool heat pump continually going 
into  defrost  mode  and  the  installation  will  need  to  be  corrected  by  the 
owner.  This situation is not covered by the warranty. 

Содержание Ultra

Страница 1: ...t Une installation inadéquate annulera la garantie Notice to Installer Avis à l installateur This manual contains important information about the installation operation and safe use of this product Once the product has been installed this manual must be given to the owner operator of this equipment Ce manuel contient des informations importantes sur l installation l exploitation et l utilisation s...

Страница 2: ...___ Compressor Starts and Stops ____________ There Is Water Around the Pool Heat Pump _ Pool Heat Pump Has Ice Formed On the Evaporator Coil _________________ Pool Heat Pump Is Not Heating ___________ Analysis Chart ________________________ Circuit Breaker Trips ___________________ Pool Heat Pump Is Noisy ________________ The Temperature Shown on Pool Heat Pump Is Not the Same than the Pool Thermo...

Страница 3: ...ded for proper operation and heating Please refer to the section Location on the following page IMPORTANT Usage of Chemical Products Never add liquid chlorine granular chlorine or slow dissolving tablets pucks into the skimmer basket This high concentration of chemicals should be avoided Water quality standards that must be strictly adhered to Warranty can be voided if not maintained within these ...

Страница 4: ...ir is pulled through the evaporator coil and discharged through the top or front grill Clearances should be allowed in front and around the unit for unrestricted air discharge and service access See Figure 1 and Figure 2 Re circulation of cold discharged air back into the evaporator coil will greatly reduce the unit s heating capacity and efficiency Pool Heat Pump Pg 06 No obstruction above Pool H...

Страница 5: ... MUST be installed between the pool heat pump and any automatic chlorinator to prevent highly chlorine concentrated water from flowing back to the pool heat pump when the pool pump is not running 2 Units that are located below the water level of the swimming pool may require the pressure switch to be adjusted This can be checked by the following method Switch ON the water pump and the pool heat pu...

Страница 6: ... these systems may leak stray voltage and currents into the water causing severe electrolysis This dramatically shortens the life of the pool heat pump and will void the warranty NOTE Bonding to pool pump is not required for above ground pool pumps but all other equipment must be bonded Pool water temperature must be above Atmospheric conditions must be above Model Ultra Reversible XLR All others ...

Страница 7: ...g back to the pool water temperature when all keys remain untouched for 5 seconds To change the temperature display from Fahrenheit F to Celsius C press the button C F The led below the F or C will be lit to indicate the current selection Note The pool heat pump will stop working when the programmed temperature is reached OPERATION OF YOUR POOL HEAT PUMP Pool Solar Blanket A pool solar blanket sho...

Страница 8: ...e XLR Electronic Control with Diagnostics Functioning of your Electronic Control with Diagnostics and Reversible XLR Electronic Control with Diagnostics OPERATION OF YOUR POOL HEAT PUMP Temperature Calibration It is possible to have a temperature variation between the water in the swimming pool and the reading of the pool heat pump temperature probe sensor Example the water in the pool is 26 ºC 80...

Страница 9: ... 70 F 21 C please adjust the bypass valve as shown Approx 60 of the water is circulating in the unit When the pool water temperature is between 70 F 21 C and 78 F 26 C please adjust the bypass valve as shown Approx 80 of the water is circulating in the unit When the pool water temperature is above 79 F 26 C please close the bypass valve as shown 100 of the water is circulating in the unit IMPORTAN...

Страница 10: ...the pool heat pump s heat exchanger in preparation for winter 4 Once the piping is disconnected the pool heat pump s heat exchanger MUST be emptied the use of a water vacuum cleaner is strongly recommended or if you do not have this tool you can tilt the unit 75 until all the water is out 5 It is recommended that the pool heat pump s heat exchanger is rinsed out with a gentle water spray at the in...

Страница 11: ...was condensation which is normal TROUBLESHOOTING Nothing Is Working but the Electronic Control Displays Digits or a Code 1 Identify the analyser code that the electronic control displays and refer to the section Service Analyser Codes 2 If the electronic control displays digits make sure that the electronic control is programmed correctly refer to the section Operation of your Pool Heat Pump and r...

Страница 12: ...s free of debris and leaves 3 If the evaporator is dusty or dirty clean it with a light spray of water and allow it to dry do not use high pressure it may damage the evaporator fins 4 When the unit is dry you may switch it back ON from the circuit breaker 5 Ensure that the clearances around the unit are respected 6 When the unit has been switched ON ensure the fan motor is working fan blades will ...

Страница 13: ...s coming from the pool heat pump and not from other equipment which will not be covered by the warranty e g noise coming from the bypass valve pool pump etc 3 An improper installation may cause this situation it will need to be corrected by the owner This situation is not covered by the warranty The Temperature Shown on the Pool Heat Pump Is Not the Same than the Pool Thermometer It is possible to...

Страница 14: ...ure the pool pump is switched ON Press ON OFF to restart the pool heat pump On new installations ensure the installation instructions were respected Check that the pool water level is correct that the pool pump is filled with water to the rim and that water is flowing correctly through the pool pump to the pool heat pump Check swimming pool and pool pump skimmer baskets and the drain at the bottom...

Страница 15: ...ics and reversible XLR electronic control with diagnostics Problem Action Remedy Problem Low refrigerant level in the pool heat pump or the low pressure safety control is defective Atmospheric conditions as well as the pool water temperature should not be below the minimum operating temperatures as stated below in order to obtain efficiency and avoid codes from appearing on the electronic control ...

Страница 16: ...tion stated in this section Warranty will only cover manufacturing defects All service call requests which are not of this nature must be paid by the purchaser to the service company authorized by Waterco Warranty service is to be completed by an authorized Service Center authorized by Waterco Where applicable in home service will be made available only in areas where a contracted service provider...

Отзывы: