background image

Page 21

 

WATERAX 

STRIKER-2/3 Owner's Manual   

04/2015 

 

 

21 

Assembly Procedure for Pump End 

(Similar procedure for the 25-16S, will have fewer impeller and distributor) 

 

13

14

15

16

17

18

19

20

25

21

22

23

24

26

19

(2/2)

 

 

Important:

 When reusing components, carefully inspect the parts. Ensure that key dimensions are within 

acceptable limits. Visually inspect the parts for pitting, worn vanes, damaged threads, damaged gasket 

faces, excessive corrosion, deformation, etc. Discard any component that is not within acceptable 

standards. Ensure that the components are clean before installing. 

 

Mechanical Rotary Seal:

 The mechanical rotary seal requires careful 

inspection. The seal should be discarded if there are signs of leaks or if the 

internal drive bushing is excessively deformed. The drive bushing must be 

free to rotate without contact with the brass housing. If there is contact 

between the drive bushing and the housing, the seal must be discarded.  

 

1.  Slide bearing retaining ring #16 on shaft #14 with plain face toward coupling collar.  

2.  Press bearing #17 on shaft using tool 600052. 

3. 

Carefully

 press rotary seal #18 in pump body #3 using pressing sleeve tool 700531.  

4.  Apply a small amount of dish soap on mechanical rotary seal O-ring to facilitate installation of pump 

shaft. Carefully pass end of shaft assembly through mechanical rotary seal bore. Make sure that flat 

sections of shaft line up with rotary seal drive bushing flat sections. Gently press down shaft until ball 

bearing rests firmly against shoulder in pump body. To verify that shaft has been properly installed, 

slowly rotate shaft by hand; rotary seal drive bushing should rotate with shaft. 

5.  Attach retaining ring #16 to pump body with six screws #15 to a torque value of 

22-25 in-lbs / 2.5-2.8 

Nm

. Tighten evenly. 

6.  A small amount of marine grease can be applied onto shaft to facilitate future disassembly. 

7.  Slide impeller #19 onto shaft, and engage with mechanical rotary seal. 

8.  Smear the O-rings with a suitable lubricant to facilitate assembly. 

9.  Place O-ring #25 in groove of distributor #20. 

10.  With open end of pump body in vertical position, carefully lower distributor #20 until it rests on bottom 

of body. Ensure that O-ring did not fall out of position during installation of distributor. 

11.  Slide impeller #19 into position, aligning with previous impeller. 

12.  Place O-ring #26 in groove of distributor #21. 

ID  ITEM NO  DESCRIPTION 

QTY 

25-16S 

QTY 

18-16S 

13  700006  12-17 COUPLING BUFFER 

14  700042  18-2C PUMP SHAFT FOR 18-16 

14  700066  25-2C PUMP SHAFT FOR 25-16 

15  800364  12-25 SCREW #8-32X7/16 PHILLIPS 

FLAT NYLON LOCK SS 

16  700032  12-3 RETAINING RING FOR BEARING, 

ALU. 

17  700044  12-48S DOUBLE ROW BALL BEARING 

WITH SEAL 

18  700008  12-28NS MECHANICAL ROTARY SEAL 

19  700036  12-7 IMPELLER, ALU. 

20  700014  12-6 DISTRIBUTOR, ALU. 

21  700065  12-9 DISTRIBUTOR, ALU. 

22  700074  12-11 IMPELLER, ALU 

23  600089  12-49 LOCKWASHER SS 

24  700012  12-50 LOCK NUT SS 

25  800450  12-26 O-RING 

26  800363  12-27 O-RING 

-  701169  GASKET BURASIL FOR 12-28NS SEAL 

-  701170  O-RING FOR 12-28NS SEAL 

NOTE:

 The sealed bearing eliminates pump failure dangers related to improper 

greasing by completely removing the need to grease the pump end bearing. 

Drive bushing 

shoulders in 

contact with 

seal housing; 

seal must be 

discarded.

Содержание STRIKER-II Series

Страница 1: ...STRIKER II AND STRIKER 3 Owner s Manual Publication Date 04 2015 Publication Number 701223 Rev 2...

Страница 2: ...WATERAX Inc assumes no responsibility for any omissions or errors that may appear in this document or for any damages that may result from the use of information contained herein The following are tr...

Страница 3: ...ctric Starters and Control Panels 7 Operating STRIKER 2 3 Series Pumps 8 Pre Operation Checklist 8 Flooded Suction 8 Drafting 9 Priming the Pump 10 Startup and Discharge 11 Shutdown 11 Cold Weather Op...

Страница 4: ...d follow all Personal Safety Advisories Warnings Always wear eye and ear protection when operating the pump unit Do not operate if mentally or physically fatigued Always inspect hoses and piping to av...

Страница 5: ...ual Always check for sufficient oil quantity in the engine crankcase before use see engine manual for details on checking the oil level as well as for the type of oil to use If applicable always check...

Страница 6: ...roduct guide technical notes links to the engine manufacturer s manuals news and other updates about WATERAX and its goods and services Abbreviations and Terms The following terms and abbreviations ar...

Страница 7: ...eries include Quick release clamp and swappable pump ends for minimal equipment downtime and inventory Sealed bearing to eliminate pump end greasing in the field Belt drive system for reliable low mai...

Страница 8: ...ERAX or from third party vendors for example control panels batteries and fuel lines You will also require hoses and nozzles as well as other fire apparatus plumbing which can be purchased through you...

Страница 9: ...ll as any other part of the pump or engine that is frequently accessed or inspected valves panels primers filters etc Make note of components that become hot when operating such as mufflers and engine...

Страница 10: ...that the equipment requires repair Remember that damaged equipment can expose you to safety hazards Flooded Suction Use this procedure if you are taking water from a hydrant another pump or a closed...

Страница 11: ...ump s ability to efficiently draft water The following limitations should be taken into account Water temperatures above 35 C 95 F can cause noticeable loss in pump performance Barometric pressures be...

Страница 12: ...Open the priming cap and fill pump with water manually 2 Firmly tighten priming cap 3 Pump can also be primed by jerking the suction hose until water flows from the pump s discharge port Guzzler Prim...

Страница 13: ...ge line left slightly open to allow fresh water to continue to enter the pump 3 Discharge water Once the pump is primed and with the engine running you can begin to discharge water a Slowly open the d...

Страница 14: ...ection WARNING Before doing any maintenance to the pump always ensure that the equipment cannot be accidentally started Follow any apparatus and or departmental procedures or guidelines in regards to...

Страница 15: ...e leakage is in the pump Air Trapped in Suction Pump Intake Line Check that no part of the suction hose or piping is higher than the pump intake Pump suction hose and piping must be laid out with a co...

Страница 16: ...ake hose was purchased check that they provide adequate supply to the pump to meet the performance desired If the pump was purchased used check that the actual configuration will achieve the desired p...

Страница 17: ...R 3 4 SHAFT 1 12 600151 PART 6 KEY 3 16 SQUARE S S 1 13 600124 B 7544 DRIVE CARRIER ASSEMBLY COMPLETE 1 14 800527 FAST 2 SCREW 3 8 16X1 HEX CAP ZINC DICHROMATE 4 15 600063 212 170P CLAMP ASSEMBLY ALU...

Страница 18: ...6 DRAIN HOLE TO BE FACING DOWN Figure 2 Exploded view of drive hub assembly item no 600124 Installing the Drive Assembly Before Installation Read and follow all instructions thoroughly and carefully E...

Страница 19: ...e and ensure proper alignment W DF 3 Align the non threaded holes of the bushing to the threaded holes of the driver pulley Insert the cap screws into the threaded holes of the pulley and turn them by...

Страница 20: ...nding hole on the front cover and partially insert the front cover onto the dowel pin 12 Using the top dowel pin as a pivot point swing the front cover and align the second dowel pin with the correspo...

Страница 21: ...tates the servicing of pump units and minimizes down time in the field by allowing the quick replacement of pump ends To remove pump from engine 1 Lift pump clamp lever 2 Release tension adjusting kno...

Страница 22: ...1 1 6 600380 12 12A SUCTION NOZZLE INCLUDES 12 40 1 1 7 800359 12 39 SCREW 1 4 28X9 16 SLOT FILLISTER SS 8 8 8 800360 12 38 LOCKWASHER 1 4 SPLIT SS 9 9 9 700022 A 5537 PROTECTIVE CAP FOR 2 SUCTION 1 1...

Страница 23: ...en properly installed slowly rotate shaft by hand rotary seal drive bushing should rotate with shaft 5 Attach retaining ring 16 to pump body with six screws 15 to a torque value of 22 25 in lbs 2 5 2...

Страница 24: ...e milled slot in the shaft 17 Place O ring 5 in groove of suction cover 6 Press cover into pump body until it rests on distributor 18 Install suction cover using screws 7 and lockwashers 8 Tighten scr...

Страница 25: ...d to remove the key switch from the engine and store it in a safe location if equipped with an XCP Original Engine Wiring Configuration To revert back to the Original Engine Controls refer to the inst...

Страница 26: ...Page 24 WATERAX STRIKER 2 3 Owner s Manual 24 04 2015 FastWire Wiring Diagrams WIRING FOR GASOLINE PUMPS Pins 7 8 connected on GX630 engine only...

Страница 27: ...74 38 91 mm Impeller height 12 11 1 334 1 343 in 33 88 34 11 mm Distributor vane diameter 3 740 3 770 in 95 00 95 76 mm Distributor bore 0 938 0 957 in 23 83 24 31 mm Distributor rear hub diameter 2...

Страница 28: ...Page 26 WATERAX STRIKER 2 3 Owner s Manual 26 04 2015 Notes...

Страница 29: ...Page 27 WATERAX STRIKER 2 3 Owner s Manual 04 2015 27...

Страница 30: ...Page 28 WATERAX STRIKER 2 3 Owner s Manual 28 04 2015...

Страница 31: ...ith the Seller s product manuals and supplemental instructions and guidelines as set out in full at www waterax com eng warranty d failure due to compliance with a specification or design provided or...