TROUBLESHOOTING - CLP
PROBLEM
POSSIBLE CAUSE
SOLUTION
NO FLOW
OF WATER
INTO THE CLP
Control switch not in "ON" position
a. Mode switch turned to "HAND" position
b. Sump pump switch not turned to
"AUTO" position
Turn switch to "ON" position.
a. Turn to "AUTO" position.
b. Turn to "AUTO" position.
Power not turned "ON" at breaker box
Turn "ON" power at breaker box.
Float on sump pump in down position
Add water to pump.
Debris in sump impeller
Unplug pump and remove from container.
Flow valve closed
Open valve.
Dirt lodged in control valve
Clean as needed.
Frozen water in lines or valves
Thaw out with warm water.
WATER FLOWING
OVER CLP
Tank not level
Level tank.
Water coming into the CLP faster than 5 -
30 gpm
Adjust fl ow control valve.
Discharge line plugged
Remove obstruction.
Pump not wired in
Wire in pump.