8.913-970.0 - L • WATERMAZE CLP 5024/7034
15
W
A
TER
TREA
TMENT
SYSTEM
OPERA
T
OR’S MANU
AL
PROGRAMMING INSTRUCTIONS
Maintenance
Mode
Description
Start Time
Run Time
Program Name
1
Media Filter Backwash
12:10 a.m.
30 minutes
MMB Time 1
2
Carbon Filter Backwash
12:45 a.m.
30 minutes
CRB Time 1
3
System Recirculation
1:30 a.m.
1.5 hours
SR Time 1
4
Filter Recirculation
3:15 a.m.
1 hour
FR Time 1
5
Automatic Sludge Dump
4:16 a.m.
1 minute
P Time 1
6
Ozone Circulation
11:00 p.m.
5 hours
Oz Time 1
Maintenance Mode Description
Button
Button
Program Name
1
Media Filter Backwash
ESC
MM TIme 1
2
Carbon Filter Backwash
ESC
CRB Time 1
3
System Recirculation
ESC
SR Time 1
4
Filter Recirculation
ESC
FR Time 1
▲
▲
▲
▲
Manual Start/Run:
Overriding the automatic maintenance schedule and
manually starting any of the Modes above can be done
in two ways:
1. To manually start and run any of the six maintenance
modes as shown in the Program Schedule above,
reset the AMC time-of-day clock to the start time as
shown in the schedule. For example, to manually
start the Media Filter Backwash cycle, temporarily
reset the AMC clock to 12:00 midnight. Don't forget
to set the clock back to its true time of day.
2. Maintenance Modes 1 through 4 are used by
WaterMaze personnel to test each CLP before it
leaves the factory, these four modes can be manually
started and run by following these instructions.
a. From the date and time screen hit the
left arrow and you'll see "ESC + C" displayed.
b. From the " ESC + C" screen follow the chart
below for the mode you want to test. For example to
start the Media Filter Backwash fi rst hit the "ESC"
button followed by the up arrow (
▲
), about a 1/2
second delay between the two. Each mode will run
for 2 minutes to give time to check for proper operation,
set fl ows and etc.