41
5 SERIES 500A11 INSTALLATION MANUAL
Wiring Schematics cont.
Aurora Advanced with ECM and IntelliStart cont.
Brown
Transformer
24V
ECM
Blower
Motor
P12
P11
2
3
4
5
1
Green
16 1
12 15 10
PWM
C1
C2
R
G
33
CFM
To P2 on
Electric Heat
Board
T
RV
CC
HP
Condensate
Black(10)
Black(09)
Blue(0
8)
Blue(07)
LP
Black
Black
FP2
T
Yellow
Yellow
FP1
Orange(02)
Orange(01)
RV
Black(15)
Violet(14)
Green(11)
Brown(23)
NOTE 2
NOTE 1
Unit Power
208-230/60/1
Run
Capacitor
Violet(42)
Blue(24)
Yellow(25)
Green/Yellow(28)
Black/White
Yellow
Red
208V
G
Black(3)
Black(2)
Gray/White(4)
1
C
2
4
3
2
Black(21)
PB2
1
3
2
Blue
240V
Black
UltraTech
Optional
RCP
CS
Blue
Blue
5A Circuit Breaker
5A Circuit Breaker
Violet(8)
Violet(7)
Red
C
S
R
L2
L1
CC
Blue
Tan
(16)
Black
T2
T1
Thermostat
R
C
Y1
O
DH
Y2
G
W
LO
02/14/13
97P840-08
Black(20)
Black(22)
Orange
BLOWER
CURRENT
TRANSDUCER
(CT)
CT
Black/White(5)
Run Winding
Active
Start
Common
IntelliStart
Pink
Blue
CT
Black
NOTE 4
Traditional
Thermostat
AID Tool
Communicating
Thermostat
NOTE 3
DESCRIPTION
SW2-4
SW2-5
Cycle with Blower
ON
ON
Cycle with Compressor
OFF
OFF
Water Valve Slow Opening
ON
OFF
Cycle with Comm. T-stat Hum Cmd
OFF
ON
ABC SW2 Accessory Relay
Slow Flash
Fast Flash
Flash Code
Flash Code 19
Alarm - Low Loop Pressure
Flash Code 21
Fault - Communication ECM Fan Motor Error Flash Code 22
Alarm - Home Automation 2
Flash Code 24
Fault - EEV Error
Flash Code 25
Fault - Critical Communication Error
Alarm - Hot Water
Flash Code 15
Fault Variable Speed Pump
Flash Code 16
Fault LED (LED 1, Red) Cont.
ESD
Flash Code 6
Future Use
Flash Code 7
Alarm - Home Automation 1
Flash Code 23
Future Use
Flash Code 17
Non-Critical Communication Error
Flash Code 18
Future Use
Flash Code 12
Non-Critical AXB Sensor Error
Flash Code 13
Critical AXB Sensor Error
Flash Code 14
Future Use
Flash Code 9
Compressor Monitoring
Flash Code 10
Fault- FP1 and FP2 Sensor Error
Flash Code 11
Reserved
Flash Code 6
Condensate Overflow Lockout
Flash Code 7
Over/Under Voltage Shutdown
Flash Code 8
Future Use
Flash Code 3
Future Use
Flash Code 4
Load Shed
Flash Code 5
OFF
Input Fault Lockout
Flash Code 1
Freeze Detection - FP1
Flash Code 5
Flash Code 2
Low Pressure Lockout
Flash Code 3
Freeze Detection - FP2
Flash Code 4
High Pressure Lockout
Dehumidification Mode
Flash Code 2
DIP Switch Overide
Slow Flash
Status LED (LED 3, Green)
Normal Mode
ON
Control is Non - Functional
OFF
Test Mode
Slow Flash
Lockout Active
Fast Flash
Aurora LED Flash Codes
1 second on and 1 second off
No Software Overide
OFF
100 milliseconds on and 100 milliseconds off
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay (Alternating Colors)
Status LED (LED1, Green)
Fast Flash
Configuration LED (LED 2, Yellow)
Fast Flash
Fault LED (LED 3, Red)
Fast Flash
Configuration LED (LED 2, Yellow)
Fault LED (LED 1, Red)
Normal Mode
CFM
P13
P4
SW1
P5
JW2
P9
LO
O/B
Y2
W
DH
P8
P7
RS485 NET
RS485 NET
P6
RS485 EXP
P3
SW2
On
Future Use
L Output Type
CC – Dual/Single
Acc – Dip 5
Acc – Dip 4
RV – B/O
FP2 – 15
°F/30°F
FP1 – 15
°F/30°F
Com1
LED5
Com2
LED5
Test Mode
F1-3A
P1
C
PWM
1
2
3
4
5
6
7
8
ALM
ALG
ACC COM
ACC NO
ACC NC
R
C
G
Y1
EH2
C
EH1
C
CO
C
R
-
+
C
R
-
+
Off
Fault
LED1
R
Status
LED3
Config
LED2
CC2
CC
F
C
R
F FG CC CCG
CC2
HI
CC2
LO
CC2
G
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS
Aurora Base Control
(ABC)
K1-RV Relay
K2-CC Relay
K3
-CC2 Relay
K4-Fan Relay
K5-Alarm
Relay
K6-Acc
Relay
F
R
C
CC
G
Y1
C
R
ES
LS
P2
EH1
Y
G
G
G