5 SERIES 500A11 INSTALLATION MANUAL
Aurora Control System
NOTE:
Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora
Interface and Diagnostics (AID) Tool for additional information.
To check the unit control board for proper operation:
1. Disconnect thermostat wires at the control board.
2. Jumper the desired test input (Y1, Y2, W, O or G) to the
R terminal to simulate a thermostat signal.
3. If control functions properly:
• Check for thermostat and field control wiring (use
the diagnostic inputs mode).
4. If control responds improperly:
• Ensure that component being controlled is
functioning (compressor, blower, reversing
valve, etc.).
• Ensure that wiring from control to the component
is correct.
• Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide:
Aurora Interface and Diagnostics (AID) Tool for
additional information.
Troubleshooting
Refrigerant Systems
To maintain sealed circuit integrity, do not install service
gauges unless unit operation appears abnormal. Compare
the change in temperature on the air side as well as the
water side to the Unit Operating Parameters tables. If the
unit’s performance is not within the ranges listed, and the
airflow and water flow are known to be correct, gauges
should then be installed and superheat and subcooling
numbers calculated. If superheat and subcooling are
outside recommended ranges, an adjustment to the
refrigerant charge may be necessary.
NOTE:
Refrigerant tests must be made with hot water
generator turned “OFF”. Verify that air and water flow rates
are at proper levels before servicing the refrigerant circuit.