47
5 SERIES 500A11 INSTALLATION MANUAL
Wiring Schematics cont.
Aurora Base with ECM and IntelliStart cont.
97P840-02 6/22/12
PB2
Violet
Blue
With optional ' EA' Series
2
3
HE1
TS1
HE2
TS2
HE3
TS3
HE4
TS4
Pink
Yellow
Black
Gray
Pink
Yellow
Black
Gray
Gray
Yellow
Pink
Black
Pink
Yellow
Black
Gray
Green
P9
ER1
ER2
ER3
ER4
NO
NO
NO
NO
Brown
Orange
5
4
EA Series PCB
P2
1
L2
L1
L2
L1
G
G
Circuit 1
Circuit 2
NOTE 3
208-230/60/1
208-230/60/1
Auxiliary Electric Heat Power
Green
Typical schematic shown
Auxiliary Electric Heat
ECM
Blower Motor
P11
2
3
4
5
1
P12
16 1
12 15 10
PWM
C1
C2
R
G
33
CFM
C
1
2
3
4
L1
L2
Single Disconnect Power
208-230/60/1
Aux Elect Power
208-230/60/1
L1
L2
L1
L2
Unit Power
208-230/60/1
CSA installed units only
Local codes may require a single
source of power supply
Breaker box
furnished by
installer
Circuit Breakers
F
P13
CFM
C
3
PWM
P13 on ABC Board
P3 on ABC Board
P3
EH2
C EH1 C
CO
Condensate
Brown
Orange
P1
4
1
2
3
C
EA Staging
NOTE 5
G
G
G
G
NOTE 4
Notes
1 - Switch blue and red wires for 208V operation.
2 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly)
when single source power is required.
4 - When installed, the Auxiliary Heat powers blower and controls.
5 - For additional Auxiliary Heat staging place jumpers as shown.
6 - Wires provided for Auxiliary Heat low voltage control. Wires are
secured at blower.
Aurora LED Flash Codes
Slow Flash 1 second ON and 1 second OFF
Fast Flash 250 milliseconds ON and 250 milliseconds OFF
Flash Code 250 milliseconds ON and 250 milliseconds OFF with a 10 second pause before repeating
Random Start Delay (Alternating Colors)
Configuration LED (LED2, Yellow)
Status LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fast Flash
No Software Override
OFF
Fast Flash
DIP Switch Override
Slow Flash
Fault LED (LED3, Red)
Fast Flash
Fault LED (LED1, Red)
Status LED (LED3, Green)
Normal Mode
OFF
Normal Mode
ON
Input Fault Lockout
Flash Code 1
Control is Non-functional
OFF
High Pressure Lockout
Flash Code 2
Test Mode
Slow Flash
Low Pressure Lockout
Flash Code 3
Lockout Active
Dehumidification Mode
Fast Flash
Future Use
Flash Code 4
Flash Code 2
Freeze Detection - FP1
Flash Code 5
Future Use
Flash Code 3
Reserved
Condensate Overflow Lockout
Flash Code 6
Future Use
Flash Code 4
Flash Code 7
Load Shed
Flash Code 5
Over/Under Voltage Shutdown
Flash Code 8
ESD
Flash Code 6
Future Use
Flash Code 9
Future Use
Flash Code 7
Future Use
Flash Code 10
FP1 and FP2 Sensor Error
Flash Code 11
Aurora Timing Events
Event
Normal Mode
Test Mode
Random Start Delay
5 to 80 seconds
1 second
Compressor On Delay
5 seconds
< 1 second
Compressor Minimum On Time
2 minutes
5 seconds
Compressor Short Cycle Delay
4 minutes
15 seconds
Blower Off Delay
30 seconds
2 seconds
Fault Recognition Delay - High Pressure
Less than 1 second Less than 1 second
Startup Bypass - Low Pressure
2 minutes
30 seconds
Fault Recognition Delay - Low Pressure
30 seconds
30 seconds
Startup Bypass - Low Water Coil Limit
2 minutes
30 seconds
Fault Recognition Delay - Low Water Coil Limit
Fault Recognition Delay - Condensate Overflow
30 seconds
30 seconds
30 seconds
30 seconds
Thermostat Call Recognition Time
2 seconds
2 seconds
Auxiliary Heat Staging Delay
5 minutes
20 seconds
Emergency Heat Staging Delay
2 minutes
7.5 seconds
Water Valve Slow Opening
90 seconds
90 seconds
Current Transducer (CT)
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Polarized connector
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -
CO -
K5 -
K6 -
CR3 -
CR4 -
F1 and F2 -
WCL -
HE -
HP -
LP -
PB1, PB2 -
PS -
RV -
SW1 -
SW1 -
SW2 -
TS -
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
Fuses
Water Coil Limit Sensor
Heater element
High pressure switch
Low pressure switch
Power blocks
Power strip
Reversing Valve coil
DIP package 5 position AXB
TEST MODE ABC Board
DIP package 8 position ABC Board
Thermal limit switch
Legend
Relay Contacts-
N.O., N.C.
G
T
1
3
2
P
L1
PSC Fan Speed Relay
PSC Fan Power Relay
ER1 to ER4 - Aux heat stage relays
HWL -
Hot water limit sensor
SC -
Start Contactor
Start Relay
SR -
CS -
Compressor Solenoid
Breaker