WATANABE WPMZ-3 Series Скачать руководство пользователя страница 9

 

 

MODEL WPMZ-3-□□□-□□-□□□                                                                                 

 

9/12 

 

                                                                                                                                                                                                               

IM-0881-04 

13-4. 

 

PEAK VALUE HOLD FUNCTION 

This is a function which holds the maximum display value. 

PeakHold A

  holds the maximum display value of Ach 

PeakHold B

  holds the maximum display value of Bch 

PeakHold A&B

  holds the maximum display value of   

Ach and Bch

 

 

13-5. 

 

BOTTOM VALUE HOLD FUNCTION 

This is a function which holds the minimum display value. 

*

When both of the maximum value hold and the minimum value 

hold  are  ON  simultaneously,  only  the  maximum  value  hold 

becomes valid. 

Minimum hold A

  holds the minimum display value of Ach 

Minimum hold B

  holds the minimum display value of Bch 

Minimum hold A&B

  holds the minimum display value of Ach 

and Bch 

 

13-6. 

 

AMP HOLD FUNCTION 

This is a function which holds the difference between maximum 
and minimum.

 

AmpHold A

  holds that of Ach 

AmpHold B

  holds that of Bch 

AmpHold A&B

  holds that of Ach and Bch

 

 

13-7. 

 

DEVIATION HOLD FUNCTION 

This  is  a  function  which  holds  display  value  that  has  the 
maximum absolute value of difference from reference value.

 

DevHold A

  holds that of Ach 

DevHold B

  holds that of Bch 

DevHold A&B

  holds that of Ach and Bch

 

 

13-8. 

 

AVERAGE HOLD FUNCTION 

This is a function which holds average value of display value.

 

AveHold A

  holds that of Ach 

AveHold B

  holds that of Bch 

AveHold A&B

  holds that of Ach and Bch

 

 

13-9. 

 

DIGITAL ZERO FUNCTION 

This is a function which makes display value “0” as offset.

 

DigitalZeroA

    :

Execute to Ach. 

DigitalZeroB

    :

Execute to Bch. 

DigitalZeroA&B

    :

Execute to both Ach and Bch. 

 

13-10. 

 

PATTERN SELECT FUNCTION 

The  pattern  select  function  is  the  function  which  switches  the 

pattern number to use for measurement. By using pattern select 

1-3, Up to 8 patterns can be switched. 

Function 

Name 

Selected pattern No. 

pattern No. in use

 

Pattern 

select1 

Open 

Short 

Open 

Short 

Open 

Short 

Open 

Short 

Pattern 
select2

 

Open 

Open 

Short 

Short 

Open 

Open 

Short 

Short 

Pattern 
select3

 

Open 

Open 

Open 

Open 

Short 

Short 

Short 

Short 

Open

pattern select terminal is open or connected to “1” level. 

Short: pattern select terminal is shorted to COM terminal or 
connected to “0” level.

 

 

13-11. 

 

DISPLAY CHANGE FUNCTION 

The  display  change  function  is  the  function  which  switches 
display and performs same action of DISP key.

 

 

13-12. 

 

TREND LOG FUNCTION 

   

Trend log function is to acquire the alarm log any time by   

          external control It is a function to execute with. While data is 
          being acquired, the trend screen displays the clock mark The 
          icon will light up. 
 

13-13. 

 

WAVE COMPARE FUNCTION 

This is a function which start/stop wave comparison. 

WaveCompA

    :

Order that of Ach. 

WaveCompB

    :

Order that of Bch. 

 

13-14. 

 

MULTI HOLD FUNCTION 

This is a function which start/section switch/stop multi hold. 

MultiHoldA

    :

Order that of Ach. 

MultiHoldB

    :

Order that of Bch. 

 
 
 

14. 

 

SHORTCUT FUNCTION 

External control functions are registered to arrow keys and are 
performed not by the terminal control but by the operation of the 
keys 

14-1. 

 

REGISTERING SHORTCUTS 

External control functions which would be performed by 
shortcuts are assigned to arrow keys by the following steps. 
These functions below are registered by default. 

1ch product 

Key 

Default function 

 

AutoAdjustA * 

 

None 

 

DigitalZeroA 

 

ManuAdjustA * 

    *Only for straingauge input 

2ch product 

Key 

Default function 

 

AutoAdjustA 

 

 

AutoAdjustB 

 

 

DigitalZeroA 

 

DigitalZeroB 

   

*Only for straingauge input 

 

14-2. 

 

PERFORMING SHORTCUTS 

A shortcut function is performed by holding down the arrow key 
which an external control function is registered for 1 second. 
An active function becomes inactive by holding down the arrow 
key which the function is registered for 1 second. 
 

15. 

 

MEASURE MODE 

Select measure mode

   

(Setting)→4.System→MeasureMode 

Setting

: 

Default/MultiHold/WaveCompare 

15-1. 

 

Default 

Perform normal measurement. 

 

15-2. 

 

Multi hold

 

   

In the multi hold mode, measurements are divided into four 

sections of section 1 to section 4, arbitrary hold settings are set 
to  each  section,  and  comparison  output  is  performed  by  hold 
value  in  each  section  and  comparison  judgment  value  set  for 
each section, respectively. 
 
Parameter 

1st Layer 

2nd Layer 

3rd Layer 

1.Input 

MultiA Base 

 

MultiB Base 

PatternSelect 
SectionSwitch 
SectionTimerS1

S4 

CompleteOutput 
AlarmColorS1

S4 

MultiA 

S1

S4 

 

MultiB 
S1

S4 

PatternSelect 
HoldStartCond. 
Threshold 
ThresholdOnDir 
ThresholdTimeout 
TimeoutOutput 
DelayTimer 
HoldType 
DevBaseValue 
DifValue 
DifMag 
InfTimeA 
InfTimeB 
InfValueZ 
CompOutput 
CompAlarmCond. 
CompJudgeValue 
CompTiming 
NoDetected 

3.Display 

DispSelect 

MultiSelect 

For  detail  and  how  to  use  this  mode,  please  refer  to  the 

detailed manual which can be downloaded from our home page.

 

 
 
 
 

Содержание WPMZ-3 Series

Страница 1: ...RTU Input Ach Input Bch GO output GO output 2 Do not wire the power supply line input signal lines and output signal lines near noise sources or relay drive lines 3 Bundling or containing in a same d...

Страница 2: ...ocess input Suitable wire AWG 24 to 16 GO OUT GO GND V HI LO EXC EXC A HI 20 14 15 16 17 18 19 27 21 22 23 24 25 26 connected internally connected internally 22 25 Process input GO output Ach Bch No N...

Страница 3: ...iffelenceHold AVE AveHold Hold mode Indicate hold mode with icon In addition 1ch product shows abbreviation below NORM NormalHold AREA AreaHold 3rd item Displays measured value of 3rd item 2nd item Di...

Страница 4: ...ve 32 None 2 4 8 16 32 64times Set moving average of input Offset 0 Go to screen of setting offset Only process input Fullscale 10000 Go to screen of setting fullscale Only process input ManuAdjust 0...

Страница 5: ...V 10V 1 5V 0 20mA 4 20mA Select a type of output range OutputDispValue None None Ach Bch Calc Select a ch referenced for analog output OutputScale 0 10000 0 99999 100 99999 Scaling of analog output Se...

Страница 6: ...lear Erase all alarm log 1st Layer 2nd Layer 3rd Layer setting items 4th Layer setting values Remarks Initial values Initial values 1 Input Wave Compare A Wave Compare B PatternSelect Pattern in use P...

Страница 7: ...r DispValue manually that you want to display Back to one before by press left arrow key Go to Fullscale display Near 100 calibration Operation is same as Settings are saved by pressing MENU key and b...

Страница 8: ...threshold value to judge How to set the value is shown below The following is an explanation for the compare mode of Level judgement Setting 2 Output CompareAL1 Threshold Set value with arrow keys Pre...

Страница 9: ...and performs same action of DISP key TREND LOG FUNCTION Trend log function is to acquire the alarm log any time by external control It is a function to execute with While data is being acquired the tr...

Страница 10: ...System Initialize UserDefaultSave 1 Setting each values Set all setting values which are needed as user default values 2 Saving user initial values By executing to save user default values current set...

Страница 11: ...etween Power terminals and inputs external controls comparative outputs other outputs AC1500V for 1 minute AC power and DC power Between input terminals and external controls comparative outputs other...

Страница 12: ...upper limit or lower limit value AL3 Display value AL4 upper limit or lower limit value AL4 Difference judgement mode When the maximum minimum during the fixed time exceeds the judgement value alarm...

Отзывы: