WATANABE WPMZ-3 Series Скачать руководство пользователя страница 1

 

 

 

 

MODEL WPMZ-3-□□□-□□-□□□

 

                                                                                                       

1/12 

 

                                                                                                                                                                                                                 

IM-0881-04 

 

 

 
 
 

Thank you for purchasing the WPMZ graphical digital panel meter.

   

This manual is a quick instruction manual only for preparation, 
connection and basic condition settings of the WPMZ. For the all 
functions of the WPMZ, please refer to a detailed instruction 
manual which can be downloaded from our homepage. 

For models with RS communication functions, please refer to 
"Modbus communication manual" or "RS-232C communication 
manual" which also can be downloaded from our homepage. 
 

https://www.watanabe-electric.co.jp/en/

 

 

 

Checks before suppling power, preparations, wiring 

 

     

     

                     

   

       

1. 

 

CHECKING THE PRODUCT 

1-1. 

 

MODEL CODES 

Please check that the product has been delivered matches the 
model code ordered in reference to “

19.

 

SPECIFICATIONS

”. 

 

 

2. 

 

PRECAUTIONS FOR USE 

2-1. 

 

ENVIRONMENTS AND CONDITIONS OF USE 

Please do not use the product under the following circumstances. 
It might cause malfunctions and shortening the life of the 
product. 
1

 

Ambient temperature of out of -5 to 50

°C

 

2

 

Ambient humidity of out of 35 to 85

%

, or freezing 

condensing 

3

 

Excessive dust or metal particles 
  (Storing in a dust-proof chassis and a countermeasure 
against heat dissipation are required.) 

4

 

Environment of corrosive gas, salty air or oily smoke 

5

 

Environment of much vibration or impact 

6

 

Environment of rain or water drops (except the front 
panel) 

7

 

Environment of strong electromagnetic field or much 
exogenous noises. 

 

2-2. 

 

INSTALLATION AND CONNECTION 

1

 

Please read this manual before the installation and the 
connection of wires. And they should be performed by a 
person having a specialized technique. In addition, the 
insulation class of the WPMZ is as shown by the figure 
below. Please confirm that the insulation class satisfies a 
use condition prior to the installation. 
 

Reinforced Insulation

               

Basic Insulation 

Operational Insulation 
 

AC 

power 

Comparative outputs, External 
control inputs, Analog output, BCD 
output,RS-232C 

RS-485 
Modbus 
RTU 

Input Ach 

Input Bch 

Go output 

Go output 

 

DC 

power 

Comparative outputs, External 
control inputs, Analog output, BCD 
output,RS-232C 

RS-485 
Modbus 
RTU

 

Input Ach 

Input Bch 

GO output 

GO output 

 

2

 

Do not wire the power supply line, input signal lines and 
output signal lines near noise sources or relay drive lines. 

3

 

Bundling or containing in a same duct with lines including 
noises might cause malfunctions. 

4

 

The WPMZ becomes available functionally right after 
power activation, but requires 30 minutes' warming to 
satisfy all performance requirements. 

Note: The inputs “A channel” and “B channel” may be 
abbreviated to “Ach” and “Bch” in this manual. 

 

2-3. 

 

CHECKING BEFORE USE 

Install the WPMZ under the environments and conditions of use 
which meet requirements. 
If  you  find  any  damage  to  the  product  or  any  problem,  please 
contact to your dealer or our company directly. 

3. 

 

HOW TO INSTALL (PANEL CUT DIMENTIONS) 

To install the WPMZ, panel cut dimensions are as shown by the 
figure below. 

 

 
 
 
 
 
 
 
 
 
 

4. 

 

CONNECTING TERMINALS 

4-1. 

 

BACK VIEW 

 
 
 
 
 
 
 
 
 
 
 
 
 

4-2. 

 

WIRING TO SCREWLESS TERMINALS 

 
 
 
 

 

 
Pushing  the  wire  release  button  with  a  flat-blade  screwdriver, 
insert  the wire  to  the  wire  insert  hole  deeply  and  then  release 
the button. 
(Suitable tool for pushing buttons 

flat-blade screwdriver blade 

width 2.5mm) 

 

4-3. 

 

CONNECTION FOR LOWER ROW TERMINALS 

                    (COMPARETIVE OUTPUT/EXTERNAL CONTROL 
                      INPUT, POWER) 

4-3-1

 

Comparative Output / External Control Input 

-Open-collector output products 

 
 
 
 
 
 
 
 
 
 

No. 

Name 

Description 

AL1 c 

AL1 open-collector output (collector) 

AL2 c 

AL2 open-collector output (collector)

 

AL3 c 

AL3 open-collector output (collector)

 

AL4 c 

AL4 open-collector output (collector)

 

AL+COM e 

Common terminal for PNP output (emitter) 
(NPN output : no connection) 

AL-COM e 

Common terminal for NPN output (emitter) 
(PNP output : GND for PNP) 

7,8 

COM 

Common

 

terminal for external control inputs

 

External control input No.1

 

10 

External control input No.2

 

11 

External control input No.3

 

12 

External control input No.4

 

13 

External control input No.5 

 

 

Graphical Digital Panel Meter 

WPMZ-3-□□□-□□-□□□ 

Quick instruction manual 

120mm min.

70

m

m

 m

in

.

+0

.6

-0

45

92

-0

+0.8

Ach inputs

Bch inputs

Power

Comparetive output/External control input

outputs

UPPER ROW TERMINALS

MIDDLE ROW 
TERMINALS

LOWER ROW TERMINALS

Wire insert hole

Wire release button

A

L

(c

)

5

C

O

M

A

L

(c

)

A

L

(c

)

A

L

(c

)

C

O

M

A

L

 +

C

O

M

(e

)

A

L

 -

C

O

M

(e

)

1 2 3 4

5 6 7

8 9

10 11 12 13

4

3

2

1

EXT CONTROL

PNP

NPN

Suitable wire:AWG24 to 16

*⑥、⑦、⑧:connected internally

Содержание WPMZ-3 Series

Страница 1: ...RTU Input Ach Input Bch GO output GO output 2 Do not wire the power supply line input signal lines and output signal lines near noise sources or relay drive lines 3 Bundling or containing in a same d...

Страница 2: ...ocess input Suitable wire AWG 24 to 16 GO OUT GO GND V HI LO EXC EXC A HI 20 14 15 16 17 18 19 27 21 22 23 24 25 26 connected internally connected internally 22 25 Process input GO output Ach Bch No N...

Страница 3: ...iffelenceHold AVE AveHold Hold mode Indicate hold mode with icon In addition 1ch product shows abbreviation below NORM NormalHold AREA AreaHold 3rd item Displays measured value of 3rd item 2nd item Di...

Страница 4: ...ve 32 None 2 4 8 16 32 64times Set moving average of input Offset 0 Go to screen of setting offset Only process input Fullscale 10000 Go to screen of setting fullscale Only process input ManuAdjust 0...

Страница 5: ...V 10V 1 5V 0 20mA 4 20mA Select a type of output range OutputDispValue None None Ach Bch Calc Select a ch referenced for analog output OutputScale 0 10000 0 99999 100 99999 Scaling of analog output Se...

Страница 6: ...lear Erase all alarm log 1st Layer 2nd Layer 3rd Layer setting items 4th Layer setting values Remarks Initial values Initial values 1 Input Wave Compare A Wave Compare B PatternSelect Pattern in use P...

Страница 7: ...r DispValue manually that you want to display Back to one before by press left arrow key Go to Fullscale display Near 100 calibration Operation is same as Settings are saved by pressing MENU key and b...

Страница 8: ...threshold value to judge How to set the value is shown below The following is an explanation for the compare mode of Level judgement Setting 2 Output CompareAL1 Threshold Set value with arrow keys Pre...

Страница 9: ...and performs same action of DISP key TREND LOG FUNCTION Trend log function is to acquire the alarm log any time by external control It is a function to execute with While data is being acquired the tr...

Страница 10: ...System Initialize UserDefaultSave 1 Setting each values Set all setting values which are needed as user default values 2 Saving user initial values By executing to save user default values current set...

Страница 11: ...etween Power terminals and inputs external controls comparative outputs other outputs AC1500V for 1 minute AC power and DC power Between input terminals and external controls comparative outputs other...

Страница 12: ...upper limit or lower limit value AL3 Display value AL4 upper limit or lower limit value AL4 Difference judgement mode When the maximum minimum during the fixed time exceeds the judgement value alarm...

Отзывы: