Wärtsilä JOVYSTAR COMPACT M
BAX 5480
- 27 -
9.4 Battery
CAUTION
A battery can present a risk for electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
a) Remove watches, rings or other metal objects;
b) Use tools with insulated handles;
c) Wear rubber gloves and boots;
d) Do not lay tools or metal parts on top of batteries;
e) Disconnect the charging source prior connecting or disconnecting battery terminals;
f) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source
from ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during
installation and maintenance (applicable to equipment and remote battery supplies not
having a grounded supply circuit).
Batteries installation
For battery installation please respect the prescriptions of the EN62040-1 standard, paragraph
4.5.
To obtain the battery life indicated by the battery manufacturer, the operating temperature
must remain between 0 and 25 °C. However, although the battery can operate up to 40 °C ,
there will be a significant reduction of the battery life.
To avoid the formation of any kind of potentially explosive hydrogen and oxygen mixture,
suitable ventilation must be provided where the battery are installed (see EN62040-1 annex N).
The batteries can be internal or external, however, it is recommended to install them when the UPS is
capable of charging them. Please remember that, if the battery is not charged for periods over 2-3
months they can be subject to irreparable damage.
Содержание JOVYSTAR COMPACT S BAX 5452
Страница 1: ...BAX 5452 Operating manual W rtsil JOVYSTAR COMPACT S 30 40 50 kVA...
Страница 22: ...W rtsil JOVYSTAR COMPACT S BAX 5452 22...
Страница 51: ...Operating Manual W rtsil JOVYSTAR COMPACT M 60kVA 160kVA BAX 5480...
Страница 136: ...Operating Manual W rtsil JOVYSTAR COMPACT L 200kVA BAX 5624...
Страница 175: ...W rtsil JOVYSTAR COMPACT L BAX 5624 40 Picture 23 Transferring the load Picture 24 Re start from manual bypass completed...