Wärtsilä JOVYSTAR COMPACT M
BAX 5480
- 80 -
Alarm
A25
INVERTER OFF
Description
The inverter is blocked due an operation failure.
Possible
causes
Various.
Solutions
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A26
COMMUNIC ERROR
Description
Internal error.
Possible
causes
Microcontroller communication problems.
Solutions
1. If the alarm persists, contact our Technical Support Service.
Alarm
A27
EEPROM ERROR
Description
The controller has detected an error in the parameters stored in EEPROM.
Possible
causes
Wrong parameters entered during programming.
Solutions
1. Contact our Technical Support Service.
Alarm
A28
CRITICAL FAULT
Description
An alarm has been activated which causes the shutdown of part of the UPS
(rectifier, inverter, static switch).
Possible
causes
System failure.
Solutions
1. Check which alarms are present and carry out the indicated procedures.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A29
MAINTENANCE REQ
Description
It is necessary to carry out maintenance work.
Possible
causes
The time limit since the last maintenance work has elapsed.
Solutions
1. Contact our Technical Support Service.
Alarm
A30
COMMON ALARM
Description
Common alarm.
Possible
causes
At least one alarm is present.
Solutions
1. Check which alarms are present and carry out the indicated procedures.
Alarm
A31
MBCB BUS CLOSED
Description
The manual bypass isolator is closed.
Possible
causes
Manual bypass isolator closed.
Solutions
1. Check the status of the manual bypass isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our Technical Support Service.
Содержание JOVYSTAR COMPACT S BAX 5452
Страница 1: ...BAX 5452 Operating manual W rtsil JOVYSTAR COMPACT S 30 40 50 kVA...
Страница 22: ...W rtsil JOVYSTAR COMPACT S BAX 5452 22...
Страница 51: ...Operating Manual W rtsil JOVYSTAR COMPACT M 60kVA 160kVA BAX 5480...
Страница 136: ...Operating Manual W rtsil JOVYSTAR COMPACT L 200kVA BAX 5624...
Страница 175: ...W rtsil JOVYSTAR COMPACT L BAX 5624 40 Picture 23 Transferring the load Picture 24 Re start from manual bypass completed...