14.7 Battery Test
The BATTERY TEST menu allows to carry out a short discharge test of the battery. In case the battery
is not efficient, the alarm “A10 – Battery fault” is generated at the end of the test.
BATTERY TEST?
The value on the second line is ready to be changed
NO
(1x)
BATTERY TEST?
The parameter is changed. The change is confirmed
by pressing
(ENTER)
YES
SPECIAL
The system performs a reset and returns to the
previous screen
BATTERY TEST
Possible loss of supply
This test can affect the continuity of supply to the loads if the battery is not fully charged.
14.8 System Reset
The UPS is equipped with internal protections which block the system or some of its sections. The
alarm can be cleared and normal operation can be resumed via the RESET menu. In case the failure
persists, the UPS will return to the previous failure condition.
In some cases the RESET is necessary to simply reset a failure signal, then the UPS will resume
operation.
RESET DEVICE?
The value on the second line is ready to be changed
NO
(1x)
RESET DEVICE?
The parameter is changed. The change is confirmed
by pressing
(ENTER)
YES
SPECIAL
The system performs a reset and returns to the
previous screen
RESET
Содержание JOVYSTAR COMPACT S BAX 5452
Страница 1: ...BAX 5452 Operating manual W rtsil JOVYSTAR COMPACT S 30 40 50 kVA...
Страница 22: ...W rtsil JOVYSTAR COMPACT S BAX 5452 22...
Страница 51: ...Operating Manual W rtsil JOVYSTAR COMPACT M 60kVA 160kVA BAX 5480...
Страница 136: ...Operating Manual W rtsil JOVYSTAR COMPACT L 200kVA BAX 5624...
Страница 175: ...W rtsil JOVYSTAR COMPACT L BAX 5624 40 Picture 23 Transferring the load Picture 24 Re start from manual bypass completed...