Wärtsilä JOVYSTAR COMPACT M
BAX 5480
- 75 -
16.1 Operating Status Definition
Status
S1
BOOSTER OK
Description
The rectifier section is working properly.
Operating
condition
The rectifier supplies the inverter and keeps the battery charged.
Status
S2
BATTERY OK
Description
The battery is connected to the UPS.
Operating
condition
The battery is kept charged by the rectifier and is ready to feed the inverter.
Status
S3
INVERTER OK
Description
The inverter voltage and frequency are within the allowed range.
Operating
condition
The inverter is ready to feed the load.
Status
S4
INVERTER --> LOAD
Description
The inverter feeds the load.
Operating
condition
The load is fed via the static inverter switch.
Status
S5
INV BYPASS SYNC
Description
The inverter is synchronized with the bypass.
Operating
condition
The synchronization between the inverter and the bypass is locked, and the static
switch can change over from one source to the other.
Status
S6
BYPASS OK
Description
The bypass voltage and frequency are within the allowed range.
Operating
condition
The bypass line is ready for changeover in case of inverter failure.
Status
S7
BYPASS --> LOAD
Description
Load fed by the bypass line.
Operating
condition
The load is fed by the bypass via the static switch, waiting for the inverter to restart.
Status
S9
INV MASTER SYNC
Description
The inverter is synchronized with the MASTER UPS.
Operating
condition
This status is only present on the SLAVE UPS units, and shows that the inverter is
synchronized with the signal sent by the MASTER UPS.
Содержание JOVYSTAR COMPACT S BAX 5452
Страница 1: ...BAX 5452 Operating manual W rtsil JOVYSTAR COMPACT S 30 40 50 kVA...
Страница 22: ...W rtsil JOVYSTAR COMPACT S BAX 5452 22...
Страница 51: ...Operating Manual W rtsil JOVYSTAR COMPACT M 60kVA 160kVA BAX 5480...
Страница 136: ...Operating Manual W rtsil JOVYSTAR COMPACT L 200kVA BAX 5624...
Страница 175: ...W rtsil JOVYSTAR COMPACT L BAX 5624 40 Picture 23 Transferring the load Picture 24 Re start from manual bypass completed...