Step 7 -
Connect the Thermostat
Install the thermostat in accordance with its installation
instructions
Typical Warmup Thermostat Wiring Diagram
Instructions for fitting Warmup® Thermostats can be found inside
the thermostat box. The thermostat must be connected to the main
electrical supply via a fuse, circuit breaker or ‘double pole isolator in
accordance with the wiring regulations.
The heater power cable consists of conductors coloured brown
(live), blue (neutral) and earth braid. If you are installing more than
two heaters on a single Warmup thermostat a junction box will be
required. These should be connected in accordance with current
wiring regulations by a qualified Part P electrician.
THERMOSTAT WIRING
1
Power Supply Cable 230 V AC
Wired via 30 mA RCD spur supplying power to thermostat
2
Heaters (16 amp 3,680 W max.)
Over 16 amps a contactor will have to be installed
3
Floor Sensor (No Polarity)
SENSOR
(NO POLARITY)
4IE-01-OB-01
IP33 T50
1
2
3