Wall Applications
Step 4 -
Install StickyMat 3d
™
•
Install the sensor at least
300 mm into the heated area it
will be controlling, if installing
wall heating only.
•
It should be located centrally
between parallel runs of
heating cable and not in an
area influenced by other heat
sources.
NOTE:
If installing both
floor and wall heating which
is controlled using one
thermostat, the sensor should
be installed in the floor.
•
At the end of the heating
cable, you will find a
termination joint. As with the
coldtail joint at the beginning
of the heating cable, this joint
will have to be cut into the
boards so that it sits at the
same height as the heater.
•
DO NOT
tape over the
termination joint, it must be
in direct contact and fully
embedded within the tile
adhesive/plaster being laid
over the heating cable.
6
7
•
Begin laying the mat, cutting
the mesh and turning the mat
to fit the wall area. Secure the
mat to the boards using the
self adhesive mesh or double
sided tape. If required the mat
can be stabled to the boards
using a staple gun.
NOTE:
DO NOT staple over
the heating cable.
•
Follow the installation layout
as in Step 3 to complete the
heater placement.
•
DO NOT
install the heating
cable in temperatures less
than -10°C.
5
•
Measure the resistance of
the sensor probe and record
it on the control card. If it’s
resistance is outside the
prescribed range contact
Warmup.
•
DO NOT
tape over the sensor
tip, it must be in full contact
with the heated tile adhesive
or plaster being laid over.
8