Figure 29 

Building chimney connection with hermetic split flue

Figure 30 

Use with split flue set

C

Exhaust gas discharge through the building chimney and fresh intake from outside 

with split flue sets

For room sealed appliances of the type C6 boilers

overheat combustion products temperature for flue; < 105 °C CO

2

 content at nominal 

operating conditions; 9.00 % (tol%0,5 / -0,5 % ) maximum allowable draught 
and maximum allowable pressure difference between combustion air inlet and flue gas 
outlet (including wind pressures); 120 Pa. characteristics and the applications of the 
duct system to which the boiler can be connected; condensate flow into the appliance 

is  not allowed. Maximum allowable temperature of combustion air; 40 C° maximum 

allowable recirculation rate of 10 % under wind conditions.

Attention:

 The terminals for the supply of combustion air and for the evacuation of 

combustion products shall not be installed on opposite walls of the building.

Exhaust gas discharge through the building chimney and 

fresh intake from outside with split flue sets

B

23

B

B

23P
33

Output pipe should be at least 2 m over surfaces those may be reached by 
individuals.

Under certain weather conditions, output pipe may emit water vapour;
installation should not be performed at places where this vapour may cause 
discomfort.

Attention:

 The minimum usable diameter must not be under 80 mm or equivalent for 

the vertical duct supplying the combustion air.

C

Attention:

 

a)  nominal working combustion product temperature : > 70°C max conditions 

b) overheat combustion products temperature : 105° C

c)  the minimum length of the specified connecting ducts; 1 mt / maximum length of 

the specified connecting ducts; 10 mt

d) For size/shape of the end of the fitting please refer 2.2.14. Installation with Vertical 

Flue Sets page 13, Fig.26.

e)  Please re adjust TsP Paramater P22 = Flues gas pipe length ( value 1 = 1 meter ) 

according to actual flue lenght  

f)  Its MUST to use NON RETURN valve ON the flue gas system. 

g) non-return valve function has to be checked annually by authorised service.

Information for the design of the common duct system for a type C(10) 

boiler

a)  The boiler is designed to become connected to a common duct system that is 

designed to operate where the static pressure in the common flue duct might 

exceed the static pressure in the common air duct by 25 Pa under the condition 

that n-1 boilers are running at maximum nominal heat input (Qn,max) and 1 boiler 

at the minimum heat input allowed by the controls

b) combustion product mass flow rate at maximum nominal heat input are given 

technical table.

c)  combustion product mass flow rate at minimum heat input allowed by the 

controls are given technical table.

d) G20 : CO

2

 or O2 content of the combustion products at nominal operating 

conditions 9 % ( +0,5/-0,5 )  

G30 / G31 : CO2-content; 10.00 % ( tolerance : +%0,5 / -0,5 % )

e)  minimum allowable pressure difference between combustion product outlet and 

air inlet shall be declared as -200 Pa (including -100 Pa wind pressure).

General for connection of a type C(10) boiler to a common duct system

Characteristics and the applications of the common duct system to which the boiler 

can be connected, with at least the following information:

a)  the flue duct system shall be CE marked and comply with EN 15502 standart 

12.2.1.4.111.2;

b) nominal combustion products temperature for dimensioning the common duct 

system shall be declared as 25 °C;

c)  the combustion product mass flow rate at maximum heat input shall be specified 

for every connection point; the terminal of the common duct shall be designed to 

induce a draft;

d) condensate flow into the boiler is allowed;

e)  maximum allowable recirculation rate of 10 % under wind conditions;

f)  the maximum allowable pressure difference between combustion product inlet 

and air outlet of the common duct system shall not be exceeded when n-1 boilers 

are running at maximum nominal heat input (Qn,max) and 1 boiler at the minimum 

heat input allowed by the controls;

g) the common flue duct shall be appropriate for an overpressure of at least 200 Pa;

h) the duct system shall not include a draft diverter.

Warning:

  the boiler if it is installed as a C (10) boiler  and IF / when the boiler is 

disconnected the air outlet and the combustion product inlet openings shall be closed 

and checked on tightness. 

C

10

Figure 31 

Exhaust gas discharge through the building chimney and fresh intake from the 

building chimney with split flue sets

Exhaust gases should be prevented from entering flue ventilation spaces.

Flue system of combi may be installed from inside the room without 
requiring intervention from the external wall. For that reason, a housing 
should be installed in the wall for lining the internal surface of channel 
wherein the output pipe passes through the wall, particularly for thick walls.

19

warmhaus.com

Содержание Enerwa Plus 2500 H

Страница 1: ...WALL MOUNTED CONDENSING SYSTEM BOILERS INSTALLATION USER MANUAL EnerwaPlus2500H EnerwaPlus3000H EnerwaPlus3500H...

Страница 2: ...EnerwaPlus 2500 H EnerwaPlus 3000 H EnerwaPlus 3500 H...

Страница 3: ...s and Installation 13 2 5 SAMPLE INSTALLATION SCHEME 14 2 6 SAMPLE INSTALLATION SCHEME 15 REMOTE CONTROL CONTROL ACCESSORIES OPTIONAL 17 2 7 COMBI FLUE CONNECTIONS 18 2 7 1 Exhaust Gas Flue Pipe Set a...

Страница 4: ...den to open The boiler must not be used by children younger 8 years or invalid persons without supervision These seals provide evidence that the replacement of bolts required for safe operation If the...

Страница 5: ...ural Gas 20 mbar G20 Available Available Not Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available Available Not Available DE YES II 2ELL3B P Natural G...

Страница 6: ...indows contact the gas emergency service 1 4 GAS LEAKAGES 187 NATURAL GAS EMERGENCY LINE HOW TO ACT IN CASE OF DETECTING NATURAL GAS ODOR DURINGEMERGENCIES INFORMATION You can visit web sites of local...

Страница 7: ...ue outlet b 2 hanger screws c 2 Dowels IV Hanger Plate Figure 4 V Exhaust Gas Flue Set optional Figure 5 Figure 1 Installation scheme Figure 3 Hanger Plate and Connection Accessories Keep packaging ma...

Страница 8: ...ith EN 12514 standard 2 2 2 Places where hermetic boilers cannot be installed Stairwells of buildings common aisles ventilation ducts garret attics emergency exit doors storage rooms and other similar...

Страница 9: ...gas valve connection is correct Flammable gas supply pipe should be able to supply correct adequate gas amount to the boiler when the boiler is at full power and be projected and sized according to f...

Страница 10: ...o provide the required flow rate for the radiator heating system depending on the critical line pressure loss Warmhaus recommends the pump complying with the European Energy Efficiency Directives ErP...

Страница 11: ...r Bathroom Drainage Lower Level Installation and Servicing Min 19 mm Min 30 mm Drainage pipe with water and air insulation Maximum length of the outer pipe shall be 3 m Insert the drainage pipe at lea...

Страница 12: ...ficiency Index EEI EN16297 3 Max delivery head in m at Q 0 25 m3 h Max volume flow H 1 11 m Max power consumption 0 20 6 90 m 2 5 m3 h 52 Max speed 5766 rpm Hydraulic operational areas ENERWA PLUS 250...

Страница 13: ...erature changes sent to radiator installation outside Temperature Sensor is activated when connected as independent from the used room thermostat typology and functions together with room thermostats...

Страница 14: ...0 mm 2 FLUE Figure 20 Enerwa Plus H Single Boiler with 1 High Temperature Zone Hot Water Storage Tank System Scheme Example INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4...

Страница 15: ...3 x 1 0 mm 2 2 Boiler Slave 1 Boiler Master 6 Boiler Slave INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4 Gas Filter 5 Vibration Isolator 6 Condensate Water Siphon and Drai...

Страница 16: ...eventual copies The content of this document is Bertelli Partners s r l s property You must not be copy or use it in whole or in part without a prior written consent by Bertelli Partn 0 MLC27 1 LT ZO...

Страница 17: ...justment and display of the boiler fault code on the display and reset it There are 6 daily programs for heating and DHW heating Daily 6 program can be applied for adjusting heating and Domestic Hot W...

Страница 18: ...installation of hermetic boilers shall be original Warmhaus flue sets and they shall be used by observing measurements and restrictions given in installation instructions In case of using exhaust gas...

Страница 19: ...pressure in the common air duct by 25 Pa under the condition that n 1 boilers are running at maximum nominal heat input Qn max and 1 boiler at the minimum heat input allowed by the controls b combusti...

Страница 20: ...er installation If one of the dimensions D E F G or H is 25mm then the remainder MUST be as shown in brackets in accordance with B S 5440 1 NOTE The distance from a fanned draught appliance terminal i...

Страница 21: ...red with the external pipe For security purposes combi suction discharge flue should not blocked even temporarily 1 90 bend 2 Sealing gasket 3 Sealing gasket 4 Centering wire 5 Exterior flue pipe 6 In...

Страница 22: ...e and exhaust pipes is 30 metres regardless from whether they are used for intake or exhaust Figure 41 Vertical flue set installation application Figure 42 Hermetic flue type installation sample Imple...

Страница 23: ...see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour from the flue te...

Страница 24: ...11 660 600013 60 100 Condensed Flue Extension L 500 mm 153 11 660 600014 60 100 Condensed Flue Extension L 1000 mm 153 11 660 600015 60 100 Condensed Flue Extension L 2000 mm 153 11 660 600016 60 100...

Страница 25: ...092 80 Condensed Twin Flue Extension Pipe L 1000 mm 153 11 660 600093 80 Condensed Twin Flue Extension Pipe L 2000 mm 153 11 660 600094 80 Twin Flue Bend 90 153 11 660 600095 80 Twin Flue Bend 45 153...

Страница 26: ...commendations are given in BS 5440 Pt 1 For IE recommendations are given in the current edition of I S 813 Domestic Gas Installations 2 If the terminal discharges onto a pathway or passageway check th...

Страница 27: ...materials or products near the boiler The exhaust gas flue set is not blocked Room thermostat s or control device is at ON position if applicable Follow the procedure given below if you are not going...

Страница 28: ...boiler operates only for domestic hot water in this mode if a boiler is fitted To switch to domestic water position 3 2 4 Resetting the Boiler Restart When the appliance shows fault blocking error pu...

Страница 29: ...be limited to the maximum temperature value e g Maximum 47 C as your boiler will have been set to Low Temperature Operation by the Authorized Service Turning off the Boiler To turn off the boiler whi...

Страница 30: ...e curves given below After connecting the Outside Temperature Sensor by means of the P04 parameter It is adjusted according to average outside temperature of your province This setting will be perform...

Страница 31: ...Safety Thermostat intervention The boiler does not operate E07 error code blinks Insufficient water in the system Pump clogging Pump Failure Pump Equipment clogging 1 First restart the boiler by push...

Страница 32: ...er radiators must be on 4 RESET the boiler and check if the problem is solved 2 Call Authorized service if the fault remains unsolved E 21 Delta Temperature Radiator Heating supply and Return TSP 82 v...

Страница 33: ...rvice if fault remains unsolved E 78 Maximum regulating current value is reached The boiler does not operate E78 error code blinks Gas Supply Pressure Wearing or corrosion of electrode Mixing of flue...

Страница 34: ...ved E 93 Failed to regulate combustion temporary The boiler does not operate E93 error code blinks Wearing or corrosion of electrode Mixing of flue gas with fresh air Clogging in the flue or incorrect...

Страница 35: ...S This warranty provided by WARMHAUS does not include fixing or eliminating faults caused by use of the appliance for purposes other than intended use as well as the conditions specified below 1 Damag...

Страница 36: ...perature C 25 47 25 47 25 47 Operating Pressure Maximum bar 3 3 3 Operating Pressure Minimum bar 0 5 0 5 0 5 Expansion tank useful volume bar 8 10 10 Pump pressure at 1000 l h flow rate mH2O 5 5 5 5 5...

Страница 37: ...t output at 30 of rated heat output and low temperature regime 1 P1 kW 4 16 4 87 5 71 Seasonal Space Heating Energy Efficiency s 92 92 92 Useful efficiency at rated heat output and high temperature re...

Страница 38: ...70 28 70 28 7 Minimum heat input Qn kW 3 75 3 59 3 75 t 80 60 Maximum heat output Pn kW 28 28 01 28 Minimum heat output Pn kW 3 5 3 5 3 3 B 23 B 23P B 33 C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 20...

Страница 39: ...33 7 33 7 Minimum heat input Qn kW 4 35 4 35 4 35 t 80 60 Maximum heat output Pn kW 33 02 33 02 32 8 Minimum heat output Pn kW 4 1 4 1 4 1 B 23 B 23P B 33 C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 2...

Страница 40: ...4 25 24 25 24 25 Minimum heat input Qn kW 3 5 2 8 3 5 t 80 60 Maximum heat output Pn kW 23 7 23 7 23 6 Minimum heat output Pn kW 3 0 2 5 3 3 B 23 B 23P C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 20 MB...

Страница 41: ...41 Enerwa Plus 2500 H 54 Enerwa Plus 3000 H 33 50 Enerwa Plus 3500 H 41 warmhaus com...

Страница 42: ......

Страница 43: ...been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject...

Страница 44: ...L MOUNTED CONDENSING SYSTEM BOILERS INSTALLATION AND USER MANUAL Enerwa Plus H Montaj Kullan m K lavuzu kodu 150 11 606 000065 Revizyon numaras R00 07 2019 EnerwaPlus2500H EnerwaPlus3000H EnerwaPlus35...

Отзывы: