Leak-tightness of the drainage connection of the condensation
line shall be ensured. However, pour approximately 1-liter water
into the internal flue prior to fitting the flue bend of the flusher in
the boiler against the gas leak risk during start-up. Thus, exhaust gas
leakage will be prevented thanks to the water in the flusher.
Slope of the condensate water hose and line shall always be downwards
2.3.6. Checks for Start-up of the Boiler
Start-up of the boiler must be carried out by Warmhaus Authorized Service in
order to commence warranty of the boiler. Preliminary preparations shall have
been performed prior to request for authorized service appointment.
- Gas supply approval certificate shall have been obtained from your local gas
authority for your gas line.
- The connection of the boiler by using 2 or 3 ampere fuse must be in place.
- Make sure that there is no electricity power loss in your house.
- Make sure that there is no city water cuts in your house.
- Ensure that water is supplied to the heating system and the boiler manometer
shows 1,2-1,5 bar pressure
Min Ø 19 mm
Min Ø 19 mm
Drainage and Ventilation Pipe
≥ 100
Figure 2.23
Connection of Condensate Drainage Pipe to
Internal Soil & Vent Stack
Figure 2.24
Connection of a Condensate Drainage Pipe
Downstream of a Sink, Basin, Bath or Shower Water Trap to
Internal Soil Vent Stack
Minimum
connection
height
up to 3
storeys
Sink/basin/
bath or
shower
Drainage and Ventilation Pipe
Figure 10
Connection of the Condensate Water Drainage Pipe to Internal Drainage and
Ventilation Pipe
Min Ø 19 mm
Min Ø 19 mm
Drainage and Ventilation Pipe
≥ 100
Figure 2.23
Connection of Condensate Drainage Pipe to
Internal Soil & Vent Stack
Figure 2.24
Connection of a Condensate Drainage Pipe
Downstream of a Sink, Basin, Bath or Shower Water Trap to
Internal Soil Vent Stack
Minimum
connection
height
up to 3
storeys
Sink/basin/
bath or
shower
Drainage and Ventilation Pipe
Figure 11
Connection of Condensate Water Drainage Pipe at Indoor Bathroom Drainage
Lower Level
27
Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 12
Outside Connection of Condensate Water Drainage Pipe
27
Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 13
Typical Connection Method of a Condensate Water Drainage Pipe (refer to
detailed instructions of the pump manufacturer)
27
Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 14
Connection of Condensate Drainage to Drainage and Ventilation Pipe
11