Installation and Servicing

 

SECTION 2 - INSTALLATION

Outdoor flusher

Condensate Water Drainage Pump

(Refer to detailed instructions of the pump manufacturer)

Min Ø 19 mm 

Inner 

Pipe

75

Min Ø 19 mm 

Inner pipe

Min Ø 30 mm 

Inner pipe

Air hole

Combined waster 

and rain water 

drainage pipe

43 mm 90º 

male/female bend

Water / Air 

proof 

insulation

68 mm Ø PVCU

Fitting

Min Ø 19 mm 

Min Ø 30 mm 

Drainage pipe with water 

and air insulation

Maximum length of 

the outer pipe 

shall be 3 m.

Insert the drainage pipe 

at least 25 mm into the tube 

located outdoors

Pebble

≥ 500

≥ 25

Required 

distance for 

minimum 3-storey 

buildings

Drainage and 

Ventilation Pipe

Min Ø 19 mm   

Water / Air proof 

insulation

Outdoor flusher

Min Ø 19 mm 

Inner pipe

75 mm flusher 

bathroom/shower 

drainage combined 

with other drainage 

lines

Minimum 30 mm

Inner pipe

Water / Air 

proof 

insulation

≥ 25 Distance under grid

45º pipe 

termination

75

≥ 100

Figure 2.25

Connection of a Condensate Pump Typical 

Method (see manufacturers detailed instructions)

Figure 2.26

Connection of condensate Drainage Pipe to 

External Soil & Vent Stack

Figure 2.27

Connection of a Condensate Drainage Pipe to an 

External Rainwater Downpipe (only combined foul/rainwater 

drain)

Figure 2.29

Connection of a Condensate Drainage Pipe to an 

External Purpose Made Soak Away.

Figure 2.28

Connection of Condensate Drainage Pipe 

Upstream of a Sink, Basin, Bath or Shower Waste Trap to 

External Drain, Gulley or Rainwater Hopper

INS

T

ALL

A

TION

CONDENSATE............ CONT’D

45º cross-

sectional drainage 

pipe outlet

Open air flusher

Figure 15 

Connection of Condensate Drainage to Rain Water Drainage

27

Installation and Servicing

 

SECTION 2 - INSTALLATION

Outdoor flusher

Condensate Water Drainage Pump

(Refer to detailed instructions of the pump manufacturer)

Min Ø 19 mm 

Inner 

Pipe

75

Min Ø 19 mm 

Inner pipe

Min Ø 30 mm 

Inner pipe

Air hole

Combined waster 

and rain water 

drainage pipe

43 mm 90º 

male/female bend

Water / Air 

proof 

insulation

68 mm Ø PVCU

Fitting

Min Ø 19 mm 

Min Ø 30 mm 

Drainage pipe with water 

and air insulation

Maximum length of 

the outer pipe 

shall be 3 m.

Insert the drainage pipe 

at least 25 mm into the tube 

located outdoors

Pebble

≥ 500

≥ 25

Required 

distance for 

minimum 3-storey 

buildings

Drainage and 

Ventilation Pipe

Min Ø 19 mm   

Water / Air proof 

insulation

Outdoor flusher

Min Ø 19 mm 

Inner pipe

75 mm flusher 

bathroom/shower 

drainage combined 

with other drainage 

lines

Minimum 30 mm

Inner pipe

Water / Air 

proof 

insulation

≥ 25 Distance under grid

45º pipe 

termination

75

≥ 100

Figure 2.25

Connection of a Condensate Pump Typical 

Method (see manufacturers detailed instructions)

Figure 2.26

Connection of condensate Drainage Pipe to 

External Soil & Vent Stack

Figure 2.27

Connection of a Condensate Drainage Pipe to an 

External Rainwater Downpipe (only combined foul/rainwater 

drain)

Figure 2.29

Connection of a Condensate Drainage Pipe to an 

External Purpose Made Soak Away.

Figure 2.28

Connection of Condensate Drainage Pipe 

Upstream of a Sink, Basin, Bath or Shower Waste Trap to 

External Drain, Gulley or Rainwater Hopper

INS

T

ALL

A

TION

CONDENSATE............ CONT’D

45º cross-

sectional drainage 

pipe outlet

Open air flusher

Figure 16 

Connection of Condensate Drainage to Rain Drainage Line through Sink, 

Bathtub or Shower Drainage Pipe

Figure 17 

Pressure, flow and electricity consumption of pumps according to power capacities of boilers

GRUNDFOS UPM3 15-70 CAOD AA

CE MARK COMFORMITY WITH FOLLOWING 

RELEVANT EC DIRECTIVES

EMC Directive (2004/108/EC),

Low voltage Directive (2006/125/EC) 

Ecodesign Directive (2009/125/EC)

Power

Grundfos UPM3 15-70 CAOD AA

Energy Efficiency Index (EEI) (EN16297/3)
Max. delivery head in [m] at Q = 0,25 m

3

/h

Max. volume flow ( H: 1,11 m)
Max power consumption

 0,20

6,90 m
2,5 m3/h
52

Max. speed

5766 rpm

Hydraulic operational areas

ENERWA PLUS 2500 H

ENERWA PLUS 3000 H
ENERWA PLUS 3500 H

2.4. FITTINGS REQUIRED FOR OPERATION OF THE 

BOILER AND HEATING SYSTEM

For single or cascade use of the condensing boiler, the heating system shall be 
fitted with the fittings specified below.
• A hydraulic separator shall be used for ideal thermal and pressure distribution 
of the boiler and system, and an exchanger with plate shall be used if the 
system-side pressure is higher than the maximum pressure of boiler and/or 
oxygen barrier pipe is not used on the system side.
• Air Separator
• Mud/Debris Strainer
• Expansion Tank (If the system is separated by a plate exchanger, at least one 
expansion tank must be placed in the return line of the cascade side and the 
return line of the heating system side.)
• Filter elements (strainers) must be fitted to return line of each boiler. These 
fittings which ensure efficient operation of your heating system and provide 
longer technical life, are obligatory accessories for warranty of your appliance. 
These accessories are not supplied with the boiler.

2.4.1. The Boiler Pumps

Enerwa and Enerwa Plus H boilers are equipped with frequency converters 
and automatic air vent.

2.4.2. Electrical Connections

Ensure electrical safety of boiler by connecting to an effective earthing 
installation that follows safety instructions in force. 
Earthing shall not be performed through the neutral line on the socket in 
places without earthing! It is dangerous and unacceptable to use gas and 
water connection pipes for earthing.

WARMHAUS A.Ş. cannot be held responsible for any damage or loss to 
individuals or property arising from failing to provide earth connection of 
the boiler and not being fitted by a competent Electrician or registered 
individual in accordance with directives and standards in force in the 
country where the boiler is installed.

Also, ensure that the electricity installation complies with the maximum power 
to be supplied as indicated in technical specifications label. Boiler shall be 
energized with "X" type socketless special power supply cables. "Warmhaus 

12

warmhaus.com

Содержание Enerwa Plus 2500 H

Страница 1: ...WALL MOUNTED CONDENSING SYSTEM BOILERS INSTALLATION USER MANUAL EnerwaPlus2500H EnerwaPlus3000H EnerwaPlus3500H...

Страница 2: ...EnerwaPlus 2500 H EnerwaPlus 3000 H EnerwaPlus 3500 H...

Страница 3: ...s and Installation 13 2 5 SAMPLE INSTALLATION SCHEME 14 2 6 SAMPLE INSTALLATION SCHEME 15 REMOTE CONTROL CONTROL ACCESSORIES OPTIONAL 17 2 7 COMBI FLUE CONNECTIONS 18 2 7 1 Exhaust Gas Flue Pipe Set a...

Страница 4: ...den to open The boiler must not be used by children younger 8 years or invalid persons without supervision These seals provide evidence that the replacement of bolts required for safe operation If the...

Страница 5: ...ural Gas 20 mbar G20 Available Available Not Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available Available Not Available DE YES II 2ELL3B P Natural G...

Страница 6: ...indows contact the gas emergency service 1 4 GAS LEAKAGES 187 NATURAL GAS EMERGENCY LINE HOW TO ACT IN CASE OF DETECTING NATURAL GAS ODOR DURINGEMERGENCIES INFORMATION You can visit web sites of local...

Страница 7: ...ue outlet b 2 hanger screws c 2 Dowels IV Hanger Plate Figure 4 V Exhaust Gas Flue Set optional Figure 5 Figure 1 Installation scheme Figure 3 Hanger Plate and Connection Accessories Keep packaging ma...

Страница 8: ...ith EN 12514 standard 2 2 2 Places where hermetic boilers cannot be installed Stairwells of buildings common aisles ventilation ducts garret attics emergency exit doors storage rooms and other similar...

Страница 9: ...gas valve connection is correct Flammable gas supply pipe should be able to supply correct adequate gas amount to the boiler when the boiler is at full power and be projected and sized according to f...

Страница 10: ...o provide the required flow rate for the radiator heating system depending on the critical line pressure loss Warmhaus recommends the pump complying with the European Energy Efficiency Directives ErP...

Страница 11: ...r Bathroom Drainage Lower Level Installation and Servicing Min 19 mm Min 30 mm Drainage pipe with water and air insulation Maximum length of the outer pipe shall be 3 m Insert the drainage pipe at lea...

Страница 12: ...ficiency Index EEI EN16297 3 Max delivery head in m at Q 0 25 m3 h Max volume flow H 1 11 m Max power consumption 0 20 6 90 m 2 5 m3 h 52 Max speed 5766 rpm Hydraulic operational areas ENERWA PLUS 250...

Страница 13: ...erature changes sent to radiator installation outside Temperature Sensor is activated when connected as independent from the used room thermostat typology and functions together with room thermostats...

Страница 14: ...0 mm 2 FLUE Figure 20 Enerwa Plus H Single Boiler with 1 High Temperature Zone Hot Water Storage Tank System Scheme Example INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4...

Страница 15: ...3 x 1 0 mm 2 2 Boiler Slave 1 Boiler Master 6 Boiler Slave INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4 Gas Filter 5 Vibration Isolator 6 Condensate Water Siphon and Drai...

Страница 16: ...eventual copies The content of this document is Bertelli Partners s r l s property You must not be copy or use it in whole or in part without a prior written consent by Bertelli Partn 0 MLC27 1 LT ZO...

Страница 17: ...justment and display of the boiler fault code on the display and reset it There are 6 daily programs for heating and DHW heating Daily 6 program can be applied for adjusting heating and Domestic Hot W...

Страница 18: ...installation of hermetic boilers shall be original Warmhaus flue sets and they shall be used by observing measurements and restrictions given in installation instructions In case of using exhaust gas...

Страница 19: ...pressure in the common air duct by 25 Pa under the condition that n 1 boilers are running at maximum nominal heat input Qn max and 1 boiler at the minimum heat input allowed by the controls b combusti...

Страница 20: ...er installation If one of the dimensions D E F G or H is 25mm then the remainder MUST be as shown in brackets in accordance with B S 5440 1 NOTE The distance from a fanned draught appliance terminal i...

Страница 21: ...red with the external pipe For security purposes combi suction discharge flue should not blocked even temporarily 1 90 bend 2 Sealing gasket 3 Sealing gasket 4 Centering wire 5 Exterior flue pipe 6 In...

Страница 22: ...e and exhaust pipes is 30 metres regardless from whether they are used for intake or exhaust Figure 41 Vertical flue set installation application Figure 42 Hermetic flue type installation sample Imple...

Страница 23: ...see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour from the flue te...

Страница 24: ...11 660 600013 60 100 Condensed Flue Extension L 500 mm 153 11 660 600014 60 100 Condensed Flue Extension L 1000 mm 153 11 660 600015 60 100 Condensed Flue Extension L 2000 mm 153 11 660 600016 60 100...

Страница 25: ...092 80 Condensed Twin Flue Extension Pipe L 1000 mm 153 11 660 600093 80 Condensed Twin Flue Extension Pipe L 2000 mm 153 11 660 600094 80 Twin Flue Bend 90 153 11 660 600095 80 Twin Flue Bend 45 153...

Страница 26: ...commendations are given in BS 5440 Pt 1 For IE recommendations are given in the current edition of I S 813 Domestic Gas Installations 2 If the terminal discharges onto a pathway or passageway check th...

Страница 27: ...materials or products near the boiler The exhaust gas flue set is not blocked Room thermostat s or control device is at ON position if applicable Follow the procedure given below if you are not going...

Страница 28: ...boiler operates only for domestic hot water in this mode if a boiler is fitted To switch to domestic water position 3 2 4 Resetting the Boiler Restart When the appliance shows fault blocking error pu...

Страница 29: ...be limited to the maximum temperature value e g Maximum 47 C as your boiler will have been set to Low Temperature Operation by the Authorized Service Turning off the Boiler To turn off the boiler whi...

Страница 30: ...e curves given below After connecting the Outside Temperature Sensor by means of the P04 parameter It is adjusted according to average outside temperature of your province This setting will be perform...

Страница 31: ...Safety Thermostat intervention The boiler does not operate E07 error code blinks Insufficient water in the system Pump clogging Pump Failure Pump Equipment clogging 1 First restart the boiler by push...

Страница 32: ...er radiators must be on 4 RESET the boiler and check if the problem is solved 2 Call Authorized service if the fault remains unsolved E 21 Delta Temperature Radiator Heating supply and Return TSP 82 v...

Страница 33: ...rvice if fault remains unsolved E 78 Maximum regulating current value is reached The boiler does not operate E78 error code blinks Gas Supply Pressure Wearing or corrosion of electrode Mixing of flue...

Страница 34: ...ved E 93 Failed to regulate combustion temporary The boiler does not operate E93 error code blinks Wearing or corrosion of electrode Mixing of flue gas with fresh air Clogging in the flue or incorrect...

Страница 35: ...S This warranty provided by WARMHAUS does not include fixing or eliminating faults caused by use of the appliance for purposes other than intended use as well as the conditions specified below 1 Damag...

Страница 36: ...perature C 25 47 25 47 25 47 Operating Pressure Maximum bar 3 3 3 Operating Pressure Minimum bar 0 5 0 5 0 5 Expansion tank useful volume bar 8 10 10 Pump pressure at 1000 l h flow rate mH2O 5 5 5 5 5...

Страница 37: ...t output at 30 of rated heat output and low temperature regime 1 P1 kW 4 16 4 87 5 71 Seasonal Space Heating Energy Efficiency s 92 92 92 Useful efficiency at rated heat output and high temperature re...

Страница 38: ...70 28 70 28 7 Minimum heat input Qn kW 3 75 3 59 3 75 t 80 60 Maximum heat output Pn kW 28 28 01 28 Minimum heat output Pn kW 3 5 3 5 3 3 B 23 B 23P B 33 C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 20...

Страница 39: ...33 7 33 7 Minimum heat input Qn kW 4 35 4 35 4 35 t 80 60 Maximum heat output Pn kW 33 02 33 02 32 8 Minimum heat output Pn kW 4 1 4 1 4 1 B 23 B 23P B 33 C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 2...

Страница 40: ...4 25 24 25 24 25 Minimum heat input Qn kW 3 5 2 8 3 5 t 80 60 Maximum heat output Pn kW 23 7 23 7 23 6 Minimum heat output Pn kW 3 0 2 5 3 3 B 23 B 23P C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 20 MB...

Страница 41: ...41 Enerwa Plus 2500 H 54 Enerwa Plus 3000 H 33 50 Enerwa Plus 3500 H 41 warmhaus com...

Страница 42: ......

Страница 43: ...been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject...

Страница 44: ...L MOUNTED CONDENSING SYSTEM BOILERS INSTALLATION AND USER MANUAL Enerwa Plus H Montaj Kullan m K lavuzu kodu 150 11 606 000065 Revizyon numaras R00 07 2019 EnerwaPlus2500H EnerwaPlus3000H EnerwaPlus35...

Отзывы: