background image

11

WARMBOARD COMFORT SYSTEM  //  GAS

WARMSOURCE FLEX  

PREPARATION

Install Location

Like all gas-fired boilers, Warmsource makes some 
noise and may be disruptive if installed near a 
bedroom or common living space. Garages and 
basements are the better choice. See the Lochnivar 
Noble Manual (pg. 7-11) for additional requirements. 
Use of a drain pan is recommended.

 

Installing Distribution Lines

After the tubing and manifolds, install the manifold 
distribution lines. Sizing, layout and length of the 
piping can be found in the WCS Design Drawings.

 

f

Pressure test all distribution lines for 15 minutes  
at 100 PSI (International Mechanical Code,  
section 1208.1)

 

Minimum Clearances

This illustration shows the recommended minimum 
dimensions for the Warmsource  mechanical area. 
This image also depicts the space necessary for 
piping and mechanical components. The minimum 
depth is 40" for access and serviceability.

 

Electrical Requirements

 

f

Warmsource boiler: 160W 
•  Warmsource pump: 30-165W (varies by heat load) 
•  Smart Reset Controller (SRC): 20W 
   (own 110V GFI outlet required for Warmsource unit)

 

f

Manifold Controller (MC): 10W per loop 
(each requires own 110V GFI outlet)

 

f

Thermostat: 5W each 
(each requires own 110V J-Box)

48” (min) width recommended when including distribution lines
Maximum space between both units is not to exceed 48”

Mounting
Bracket

4

3/8

"

80K

80K

199K

2

3/4

"

5"

9"

110K

2

3/4

"

15"

150K

2

3/4

"

9

1/4

"

11

3/4

"

18"

18"

18"

12

1/2

"

15

1/4

"

2

1/2

"

9

1/4

"

11

1/4

"

13"

16"

5"

8

1/2

"

17"

2

1/4

"

15

1/2

"

1

1/2

"

4

1/4

"

8

1/2

"

15

1/2

"

4

3/4

"

8

1/2

"

17

17"

Pressure
Relief Valve

Air Vent

Air Exhaust

Air Intake

Condensate

Gas

 1-1

1/4

” Copper

(field supplied)

9"

17"

24"

2"

48”

Boiler

Warmsource

18”

24”

12”

Supply (back)
Return (front)

4

3/4

"

8

1/2

"

17"

17"

Install the Warmboard-supplied ball valves and 
hose bibs as shown in our Design Drawings  
for the proper filling and purging of air from  
the system.

Pre-plumb boiler components prior to drywall. 
Reference page 4 of this guide.

Warmsource Flex dimensions: 
80K: 17W x 24H x 17D ea.

 

110,150,199K:

 

17W x 24H x 17D, 17W x 24H x 18D

To estimate labor costs, view the boiler page 
in the WCS Design Drawings to see how the 
manifold distribution lines should be plumbed.

Содержание Warmsource

Страница 1: ...For use with Warmsource and Warmsource Flex natural gas boiler Warmsource and Warmsource Flex propane gas boiler WARMBOARD COMFORT SYSTEM 0622 Installation Guide...

Страница 2: ...no programming or commissioning and water temperatures are calibrated using our Indoor Reset algorithm 7 DO NOT adjust any boiler settings without consulting Warmboard Changes made through the boiler...

Страница 3: ...S f Install tubing some loops before walls and use the provided labels to keep track of loops and zones f Frame walls roof sheeting f Install tubing manifolds some loops f Install all 110 volt electri...

Страница 4: ...up water for evaporation f Backflow preventer required by code in many jurisdictions it prevents water in the closed loop system from mixing with the domestic water f 11 4 combo ball valve hose bib f...

Страница 5: ...3 48 2 121 4 2 281 2 33 27 33 121 2 Pressure Relief Valve Mounting Bracket Air Vent r Exhaust Air Intake ensate right Gas right Supply back Return front 9 43 8 3 48 9 43 8 3 48 2 121 4 2 281 2 33 27...

Страница 6: ...5 81 2 21 4 151 2 51 2 91 4 110K 150K 199K 171 2 11 2 199K 150K 23 4 91 4 113 4 121 2 151 4 21 2 91 4 111 4 13 16 21 4 151 2 171 2 Bottom View 80K Top View 80K 80K 5 81 2 21 4 151 2 11 2 51 2 91 4 110...

Страница 7: ...depicts the space necessary for piping and mechanical components The minimum depth is 40 for access and serviceability Electrical Requirements f Warmsource boiler 160W Warmsource pump 30 165W varies...

Страница 8: ...res two individuals to move safely Connections f Connect the PVC intake and exhaust lines gas line condensation discharge line and pressure relief discharge line per the Lochnivar Noble Manual f Plumb...

Страница 9: ...er field supplied 9 17 24 2 Supply back Return front Mounting Bracket 43 8 Pressure Relief Valve Air Vent Air Exhaust Air Intake Condensate Gas 1 11 4 Copper field supplied 9 17 24 2 Supply back Retur...

Страница 10: ...8 18 121 2 151 4 21 4 151 2 11 2 17 80K 80K 23 4 5 9 110K 23 4 15 150K 23 4 91 4 113 4 18 18 121 2 151 4 5 81 2 17 21 4 151 2 11 2 41 4 81 2 17 43 4 81 2 80K 199K 150K 23 4 91 4 113 4 18 18 18 121 2 1...

Страница 11: ...ecessary for piping and mechanical components The minimum depth is 40 for access and serviceability Electrical Requirements f Warmsource boiler 160W Warmsource pump 30 165W varies by heat load Smart R...

Страница 12: ...ure relief discharge line per the Lochnivar Noble Manual f Plumb the cold water line to the backflow preventer and the pressure reducing valve WCS Design Drawings f Plumb Warmsource Flex to the boiler...

Страница 13: ...filling the system with water for 10 15 minutes until air cannot be seen or heard escaping the hose f Close the fast fill lever then slowly close hose bib A f Manifold 1 is now complete Repeat this pr...

Страница 14: ...Warmsource will reach the target temperature in about 10 minutes f Step 4 Return to each manifold and adjust the flow rates of each loop 1 Unthread and discard the white caps from the return side of t...

Страница 15: ...ur WCS Design Drawings Controls Warmboard Controls consist of the following f 110 volt thermostats one per heating zone f 110 volt Manifold Controller one per manifold f 24 volt solenoid valve loop ac...

Страница 16: ...to behave inaccurately If there are any discrepancies regarding the thermostat or zoning contact us immediately f Remove the appropriate thermostat from the box f Grip the face of the thermostat on th...

Страница 17: ...inal connection AC1 Fan on the Smart Reset Controller SRC f Connect the wires from the AC unit to the terminal block accordingly RC 24v power red wire Y Cooling Call yellow wire G Fan green wire f To...

Страница 18: ...nutes the green lights will turn blue indicating that the actuators have opened and water is flowing to the zone f If something does not appear to be working properly consult your Warmboard Engineered...

Страница 19: ...EXCLUDED FAILURE TO INSTALL WARMBOARD PRODUCTS ACCORDING TO MANU FACTURER S INSTRUCTIONS WILL VOID ALL APPLICABLE WARRANTIES IT IS EXPRESSLY UNDERSTOOD THAT WARMBOARD IS NOT RESPONSI BLE FOR ANY CONSE...

Отзывы: