Once the system is plumbed and pressure tested with 
air (T&M Installation Guide), the next step is to fill the 
system with water and purge the air in the lines.

Air in a closed loop heating system can create noise 
and inhibit the flow of water. Follow these steps to 
save hours or days of frustration.

 

Purge Air, Fill with Water

 

Follow these steps to fill and purge air the system. 
This should be done one manifold at a time. In this 
example, we’ll begin with Manifold 1 (illustration).

 

f

Thread a discharge hose on to valve 

A

,  

and ensure the other end of the hose reaches 
the exterior of the house (or drain)

 

f

On valve 

A

, make sure the ball valve is closed  

and the hose bib is open

 

f

Close all hose bibs and ball valves on  
the remaining manifold return lines (

B

C

)

 

f

On the supply side, close the hose bib  
and open ball valve 

D

 

f

To fill Warmsource-E and the manifold 1 loops  
with water (city or well supply), lift the fast fill lever 
on the pressure reducing valve 

E

 

f

Check each loop flow meter on manifold 1 and 
confirm good flow is taking place

 

f

Continue filling the system with water for 10–15 
minutes until no air is seen, or heard, escaping  
the hose

 

f

Close the fast fill lever, then slowly close hose bib 

A

 

f

Ensure the pressure gauge located inside  
Warmsource-E reads 12–18 PSI

 

f

Manifold 1 is now complete. Repeat this  
process for each manifold (

B

C

)

Propylene Glycol

In some situations, it may be necessary to add 
propylene glycol to prevent freezing. To do this, 
open the ball valve 

D

, and add via the hose bib. 

We recommend a 10-30% mix, but refer to the 
manufacturer’s recommendation. 

ONLY

 use 

propylene glycol for freeze protection.

To fill the system with a propylene glycol/water 
solution, we recommend a Liberty 331 Portable 
Transfer Pump, or equivalent (homedepot.com).  
To maintain the propylene glycol feed for many years, 
we recommend the Axiom MF200 Pressure Pal. 

FILLING & PURGING

A
B
C
D
E
F
G

3/4

" Combo ball valve/hose bib

3/4

" Combo ball valve/hose bib

3/4

" Combo ball valve/hose bib

1

1/4

" Combo ball valve/hose bib

Fast fill lever/pressure reducing valve

Backflow preventer

1/2" ball valve

E

F

G

Manifold 1

Manifold 2

Manifold 3

A

C

B

Manifold 1

Manifold 3

Manifold 2

D

RETURN

SUPPLY

Reference the Electro Boiler Manual for allowable 
mineral levels and water quality. Filtered water or 
a corrosion inhibitor may be required.

Содержание Comfort System

Страница 1: ...For use with Warmsource E electric boiler WARMBOARD COMFORT SYSTEM 0622 Installation Guide...

Страница 2: ...e the ambient air temperature near the Warmsource E does not exceed 90 F 32 C during operation 6 Reference the Electro Boiler Manual for allowable mineral levels and water quality Filtered water or a...

Страница 3: ...s list can be a helpful when working with Warmboard S and WCS f Foundation and joist f Install Warmboard S f Install tubing some loops before walls f Frame walls roof sheeting f Install tubing manifol...

Страница 4: ...be reset with a bike pump and ball valve in the closed position f Backflow preventer required by code in many jurisdictions prevents water in the closed loop system from mixing with the domestic wate...

Страница 5: ...e piping can be found in the WCS Design Drawings f Pressure test all distribution lines for 15 minutes at 100 PSI International Mechanical Code section 1208 1 Minimum Clearances This illustration show...

Страница 6: ...it Air Eliminator 51 2 331 2 33 4 41 2 253 8 1 11 4 conduit 1 2 3 4 conduit 131 4 51 2 21 4 61 8 3 41 8 91 2 Pressure Relief Drain connection 3 4 NPT 1 11 4 conduit Air Eliminator 51 2 331 2 33 4 41 2...

Страница 7: ...all studs then fasten the unit into place Warmsource E weighs 155lbs and requires two individuals to move safely Connections f Plumb the cold water line to the backflow preventer and the pressure redu...

Страница 8: ...nue filling the system with water for 10 15 minutes until no air is seen or heard escaping the hose f Close the fast fill lever then slowly close hose bib A f Ensure the pressure gauge located inside...

Страница 9: ...lug the white Construction Mode jumper into the Sensor 2 terminal The boiler temperature can be adjusted if a higher temperature is desired Warmsource E will reach the target temperature in about 10 m...

Страница 10: ...per heating zone f 120 VAC Manifold Controller one per manifold f 24 volt solenoid valve actuators one per loop f Smart Reset Controller inside Warmsource E Installing the MC f Use the provided screws...

Страница 11: ...m to behave inaccurately If there are any discrepancies regarding the thermostat or zoning contact us immediately f Remove the appropriate thermostat from the box f Grip the face of the thermostat by...

Страница 12: ...connection AC1 Fan on the Smart Reset Controller SRC f Connect the wires from the AC unit to the terminal block accordingly RC 24 volt power red wire Y Cooling Call yellow wire G Fan green wire f To...

Страница 13: ...nutes the green lights will turn blue indicating that the actuators have opened and water is flowing to the zone f If something does not appear to be working properly consult your Warmboard Engineered...

Страница 14: ...EXCLUDED FAILURE TO INSTALL WARMBOARD PRODUCTS ACCORDING TO MANUFACTURER S INSTRUCTIONS WILL VOID ALL APPLICABLE WARRANTIES IT IS EXPRESSLY UNDERSTOOD THAT WARMBOARD IS NOT RESPONSIBLE FOR ANY CONSEQU...

Отзывы: