6.3.5 Control lines
If you wish to activate several sun shading products with one channel of the
Wisotronic, you can connect a floor distribution control or motor control units
to terminals X2 to X4 instead of a sun shading drive.
Channel 2
E
P
Channel 3
E
P
Channel 4
E
P
To the floor distribution controls or to the motor control units.
See the wiring diagrams document, art. no. 816 345
Channel 1
E
P
Wisotronic
power unit
F2
F1
F3
F4
1
9
8
7 6
4
3 2
1
4
3 2
1
4
3 2
1
Fig. 22
Connection of control lines
Terminal blocks X2, X3, X4
Permissible line cross section
0.2 to 2.5 mm
2
single-wire
0.2 to 2.5 mm
2
fine wire
Stripping length
6.5 mm
Maximum line length
200 m
WARNING
If 24 V control lines are connected to terminal blocks X2/X3/X4, the lines
must be routed at least 8 mm away from the 230 V lines. Otherwise, the
24 V lines must be doubly insulated (e.g. with silicone hoses).
Connection