Sensor Splitter
4 Connection
4.1 Connection
information
WARNING
In a permanently routed installation, there must be an in-series
disconnecting and isolating device to separate the device from the supply
voltage (switch according to TE 60335-1, Section 25.2, e.g. circuit breaker).
230 V AC lines (power lines) should not be routed between the DIN rail and
rear wall but to one side at as great a distance as possible.
The ex24-V voltage provided by the sensor splitter is exclusively in-
tended for supplying a connected weather station. If other weather stations
are connected, they need to be supplied by a separate power supply unit.
The specified lines are recommendations. As specified in VDE 0022, the
operating company and the installer are responsible for compliance with the
regulations put forth by the public utility provider and the VDE.
The wiring specified in the cable diagrams is for minimum cross sections in
copper, taking no account of the length and the resulting voltage drops.
The relevant VDE regulations must be followed when routing lines outdoors.
Furthermore, the lines must be suitable for outdoor use.
High voltage and low voltage lines must be routed separately (at least 10 cm
apart).
DANGER
Work on the 230-V network must be performed by a certified electrician
in accordance with the electrical installation regulations published by the
Association of German TElectrical TEngineers (VDTE 0100) or the standards
and regulations of the country in which the device is being installed.
NTTE
The device meets the requirements for use in domestic and business prem-
ises.