69
W&T
IP-Watcher 2x2 Digital PoE
These buttons allow triggering of all alarm messages for the
enabled alarms without the actual trigger condition having to
occur.
Clicking on the
Trigger
button tells the device that the
triggering condition for the alarm has been met. The
reachability of linked entries from the
IP Watch List
is here irre-
levant, but the actual trigger condition should still not be met.
This is simply a virtual alarm triggering.
The
ACK
button acknowledges the alarm triggered when you
clicked on
Trigger
. Acknowledgement is only possible if at least
one acknowledgement variant has been set for the alarm. If no
alarm confirmation is configured, the ACK button is greyed out.
The
Reset
button resets the artificially set trigger. This is an
absolute requirement when testing the alarms, since otherwise
an actually occurring alarm will not be recognized.
If the
Trigger
button was used to set an artificial trigger, this is
also indicated on the
home.htm
page by flashing texts. On the
home.htm
page an activated test alarm is also shown in the
message box above the alarm table.