IP-Watcher 2x2 Digital PoE
Config >> Device >> Alarm >> Alarm X
In the
Alarm Name
field enter a name for the alarm. This name
is displayed on all control and operating pages.
The check box
Alarm Enable
must be activated for the alarm to
be triggered when the trigger condition is met. To deactivate
the alarm, simply deactivate the check box again. It is then not
necessary to clear the settings.
In the
IP Watch List
block you will find all network components
which have already been added to the
IP Watch List
. Check the
box in front of the entries you want to be monitored by the
alarm.
If you assign an alarm to multiple IP addresses, a single
1
non-responding IP address is sufficient to trigger the
alarm. Is there another non-responding IP address the alarm is
triggered again.
User the parameter
Trigger Count
to specify the number of
permitted failed poll attempts.
The value
Polling Rate
determines the interval in seconds at
which the IP addresses assigned to the alarm are polled. Note
here that the attempt to poll and IP address may take up to five
seconds if it is no longer reachable.
Use the
Interval
field to determine the send interval for the
alarm.
E
is preset, which corresponds to one-time sending. Here
yhou can enter any number of minutes as a send interval.