750 XTR Series
Planning
46
System manual | Version: 2.0.0
•
Ensure clearance and creepage distances between intrinsically safe segments!
The maximum current provided by the supply module (item no.:
ü
) is
1 A. If the use of further 750-606/040-000 supply modules is required for capacity uti-
lization reasons, use four 750-616/040-000 Distance Modules to maintain the distance
between the intrinsically safe segments.
5.5.3 Ex i XTR Use in Substation Instrumentation and Control and Telecontrol
Technology or in Marine Applications
As a general rule, for standards-compliant use of the Ex i XTR I/O module in substation
instrumentation and control, telecontrol technology, railway engineering or shipbuilding-
certified operation, filter modules (item no.:
ü
) or supply filters (item
no.:
ü
Table 10: Filter Modules for 24 V Power Supply
Item No.
Name
Description
ü
24 VDC HI XTR supply filter
System and field supply with filtering (24 V, 0 V)
ü
Field supply filter 24 VDC HI NC
XTR
24 V field supply with filtering
The following power supply concepts must be observed:
When using Ex i XTR I/O modules in shipping, substation instrumentation and control and
telecontrol technology, the supply voltage of the “Power Supply 24 VDC Diagn for Ex i
XTR Modules” (item no.:
ü
) must be supplied via the corresponding fil-
ter module.
Figure 24: Power Supply Concept, Example 1
No.
Explanation
1
XTR head station
2
XTR filter module (750-626/040-000)
3
XTR “Power Supply 24 VDC Diagn for Ex i XTR Modules”
(750-606/040-000)
4
Ex i XTR I/O module
5
XTR end module