750 XTR Series
Planning
44
System manual | Version: 2.0.0
No.
Explanation
5
Power supply; 24 VDC; fuse holder; extreme
(item no.: 750-601/040-000 or 750-610/040-000)
6
Field supply filter (surge); 24 VDC; higher isolation; extreme
(item no.: 750-624/040-000)
7
Power supply; 0 ... 230 VAC/DC; extreme (item no.: 750-612/040-000)
8
XTR end module (item no.: 750-600/040-00x)
Potential Groups
U
F1
Field supply 1 (24 VDC)
U
S
System supply (24 VDC)
U
F2
Field supply 2 (24 VDC)
U
F3
Field supply 3 (24 VDC)
U
F4
Field supply 4 (230 VAC)
Marine Applications per DNV GL
• Class A: all areas except bridge and open deck
• Class B: all areas including bridge and open deck
5.5.2 Ex i XTR Applications
Some I/O modules are intended to be connected to devices located in hazardous areas.
To ensure safety and reliability in these applications, several additional requirements
must be taken into account:
• The node structure must meet the additional requirements specified below for the
power supply, as well as the requirements for clearances and creepage distances.
• The operator must obtain a prototype test certificate that confirms the correct installa-
tion of the system and store it in the control cabinet/housing.
You can find the detailed requirements in the original wording of the respective certificate
(
8
Installation Regulations Specified by Approvals [
Power Supply Requirements
For all node sections containing I/O modules for Ex i applications, the following applies:
•
Supply of the Ex i XTR I/O modules only via “Power Supply 24 VDC Diagn for
Ex
i XTR Modules”
The Ex i XTR I/O modules must only be operated in conjunction with the 24 VDC
power supply (item no.:
ü
)!
•
Do not exceed maximum current via power jumper contacts
The maximum current provided by this 24 VDC power supply is 1 A.
When configuring the system, make sure that this current is not exceeded. If it is, you
must use an additional Ex i power supply module (item no.:
ü