74 • Fieldbus Coupler 750-337, 750-338
Technical
Data
WAGO-I/O-SYSTEM
750
CANopen
3.1.8 Technical Data
System Data
Max. number of partitipants in the
CAN-network (without repeater)
110
Transmission medium
shielded Cu cable3 x 0.25 mm
2
Max. length of bus line
30 m ... 100 m
(baud rate dependent / cable dependent)
Baud rate
10 kBaud ... 1 MBaud
Fieldbus connection
750-337:
750-338:
- 5-pole male connector, series 231 (MCS)
female connector 231-305/010-000
is included
- 1 x D-SUB 9;
plug 750-963 is not included
Standards and Regulations (cf. Chapter 2.2)
EMC CE-Immunity to interference
750-337:
750-338:
- acc. to EN 50082-2 (1996)
- acc. to EN 61000-6-2 (2001)
EMC CE-Emission of interference
750-337:
750-338:
- acc. to EN 50081-2 (1994)
- acc. to EN 61000-6-3 (2001)
EMC marine applications
-Immunity to interference *
)
acc. to Germanischer Lloyd (01)
EMC marine applications
-Emission of interference *
)
acc. to Germanischer Lloyd (01)
*
)
only 750-337
Approvals (cf. Chapter 2.2)
C
UL
US
(UL508)
ABS (American Bureau of Shipping) *
)
BV (Bureau Veritas) *
)
DNV (Det Norske Veritas) *
)
Cl.
B
GL (Germanischer Lloyd) *
)
Cat. A, B, C, D
KR (Korean Register of Shipping) *
)
LR (Lloyd's Register) *
)
Env. 1, 2, 3, 4
NKK (Nippon Kaiji Kyokai)
RINA (Registro Italiano Navale) *
)
C
UL
US
(UL1604)
Class I Div2 ABCD T4A
DEMKO *
)
II 3 G EEx nA II T4
Conformity Marking *
)
*
)
only 750-337