CANopen
• 133
Network Communication
WAGO-I/O-SYSTEM 750
CANopen
4.3.4.4.10 Object
0x6411,
Analog Outputs 16 Bit
Idx
S-Idx
Name
Type
Attribute
Default Value
0x6411
0
Number analog input channels
(16Bit)
Unsigned8
RO
-
1
1. channel
Unsigned16
RW
0
....
....
....
....
....
254
254. channel
Unsigned16
RW
0
This object contains the process data of the analog output modules. Sub-index
1 contains the first analog output channel from left to right, counting starting
with the bus coupler. Sub-index 2 the second, etc.
4.3.4.4.11 Object
0x6421,
Analog Input Interrupt Trigger Selection
Idx
S-Idx
Name
Type
Attribute
Default Value
0x6421
0
Number analog input channels
(16Bit)
Unsigned8 RO
-
1
Trigger 1. channel
Unsigned8
RW
7
.... ....
....
.... ....
128
Trigger 128. channel
Unsigned8
RW
7
This object is used to define the condition of the transmission. Prerequisite for
the transmission being that a 1 is entered in object 0x6423, and consequently
the general transmission released.
Design Sub-Index 1..128:
Bit
Transmission conditions
Configuration
Sub-Index
0
Threshold value exceeded
0x6424
1
Threshold value fallen short
0x6425
2
Change of the input value exceeding the delta value for
the last transmission
0x6426
3
Reduction of the input value by more than the delta value
for the last transmission
0x6427
4
Increase of the input value by more than the delta value
for the last transmission
0x6428
5 to 7
Reserved
-
4.3.4.4.12
Object 0x6423, Analog Input Global Interrupt Enable
Idx
S-Idx
Name
Type
Attribute
Default Value
0x6423
0
Global Interrupt Enable Analog
16Bit
Unsigned8 RW
0
This object is used to control the transmission of the analog input data using
PDO. If the value is 1, the transmission is released, and it only depends on ob-
ject 0x6421 and the transmission type of the PDO. If the value is 0, no trans-
mission of the analog input data is made, independent of object 0x6421.