108 • CANopen
Network
Communication
WAGO-I/O-SYSTEM
750
CANopen
4.3.4.2.3 Object 0x1003, Pre-defined Error Field
Idx
S-Idx
Name
Type
Attribute
Default Value
0x1003
0
Number of Errors
Unsigned8
RW
0
1
Standard Error Field
Unsigned32
RO
-
:
:
: :
:
20
Standard Error Field
Unsigned32
RO
-
The sub-index 0 contains the errors currently stored in the field. If a new error
occurs, it will be entered in sub-index 1, and all errors already existing moved
down by one sub-index. A max. of 20 error entries are supported. Should more
than 20 errors occur, each time the error contained in sub-index 20 is written
over.
Design Standard Error Field:
Bit31 Bit16 Bit15 Bit0
Additional Information
Error code
The additional information corresponds to the first 2 bytes of the additional
code of the Emergency telegram. The error code coincides with the error code
in the Emergency telegram.
The complete error memory is deleted by writing a „0" in sub-index 0.
4.3.4.2.4 Object 0x1005, COB-ID SYNC message
Idx
S-Idx
Name
Type
Attribute
Default Value
0x1005 0 COB-ID
SYNC
Unsigned32
RW
0x00000080
The object defines the COB ID for the synchronization message.
Design:
Bit31 Bit11 Bit10 Bit0
Reserved (always 0)
COB-ID
4.3.4.2.5 Object 0x1006, Communication Cycle Period
Idx
S-Idx
Name
Type
Attribute
Default Value
0x1006 0 Communication
Cycle Period
Unsigned32 RW
0
The object defines the max. time in
µ
s for two subsequent SYNC messages.
The internal resolution is 2ms. If the value is 0, no SYNC monitoring is per-
formed.
4.3.4.2.6 Object 0x1008, Manufacturer Device Name
Idx
S-Idx
Name
Type
Attribute
Default Value
0x1008 0 Manufacturer
Device
Name
Visible
String
RO 750-337
The object indicates the device name of the bus coupler.