WAGO I/O System
Diagnostics 81
750-662/000-004 8FDI 24V PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
8.2
Errors and Error Types
Table 36: Errors and Error Types
Error
Error Type
Coding
Safe Inputs
Internal channel error
Channel error
0x0280
Short circuit
Channel error
0x0201
Overload clock output
Channel error
0x0286
Discrepancy time exceeded
Channel pair error
0x021E
General
Safety shutdown (internal error)
Module error
0x0219
Firmware update required
Module error
0x0231
Invalid iParameters
Module error
0x0200
Overtemperature error
Module error
0x0205
Undervoltage field supply
Module error
0x0202
Overvoltage field supply
Module error
0x0230
Overtemperature warning
Module error
0x0232
F_Dest_Add mismatch
Configuration error
0x0040
Invalid F_Dest_Add
Configuration error
0x0041
Invalid F_Source_Add
Configuration error
0x0042
Invalid F_WD_Time
Configuration error
0x0043
Non-supported F_SIL
Configuration error
0x0044
Incorrect F_CRC_Length
Configuration error
0x0045
Incorrect F_Par_Version
Configuration error
0x0046
Invalid F_CRC1
Configuration error
0x0047
Inconsistent F_iPar_CRC
Configuration error
0x004B
Non-supported F_Block_ID
Configuration error
0x004C
Invalid F parameters
Configuration error
0x0048
Error uploading iParameters
Configuration error
0x0049
Error downloading iParameters
Configuration error
0x004A
PROFIsafe CRC2 error
Communication error
0x004D
F_WD_Time expired
Communication error
0x004E
Acknowledgement required
–
0x004F