WAGO I/O System
Diagnostics 85
750-662/000-004 8FDI 24V PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Table 37: Diagnostic Messages
Message
Description
Error
downloading
Diagnostic type
Module diagnostic
Coding
0x004A
LED indicator
No indicator
Description/
remedy
Timeout when writing (downloading) the
iParameters from the iPar server. Check
whether an iPar server instance was
created for the F I/O module and whether
an appropriate data set exists.
Classification
Error
Error uploading
Diagnostic type
Module diagnostic
Coding
0x0049
LED indicator
No indicator
Description/
remedy
Timeout when saving (uploading) the
iParameters to the iPar server. Check
whether an iPar server instance was
created for the F I/O module.
Classification
Error
F_Dest_Add
mismatch
Diagnostic type
Module diagnostic
Coding
0x0040
LED indicator
Module error: red
PROFIsafe status: red
Description/
remedy
The PROFIsafe address assigned as part
of the F parameterization differs from the
one set on the F I/O module. Check the
DIP switch setting or PROFIsafe address
set using the safety editor (SEDI).
Classification
Error
F_WD_Time
expired
Diagnostic type
Module diagnostic
Coding
0x004E
LED indicator
Module error: red
PROFIsafe status: red, flashing at 1 Hz
Description/
remedy
The time between two data packets from
the safe PLC was greater than the time set
in F_WD_Time. Check the F_WD_Time
parameter and increase the value if
necessary.
Classification
Error