60
Parameterizing
WAGO-SPEEDWAY 767
767-5401 4DIO 24V DC 0.2A HS (4xM12)
Manual
Version 1.1.0
Table 31: Overview of adjustable counter parameters for the DIO Module
Parameter
Description
Start/limit value
Enter a value (0 - 65535), which is used as the start value or as a reference
to control the switching output.
Default setting: 32768
Set start/limit value
For an up counter, the "Start/limit value" is used as the limit value.
For a down counter, this value is loaded in the counter value as a start
value.
Switching output
(output X4)
Digital output
If you select this option, the "Status limit value" is output as a digital
signal (see section "Control of the Counter via Inputs and Outputs"9.1).
No*
Status limit value
Display if the limit value is reached (count direction up/down).
Display whether the limit value set (up and down counter) is reached. The
limit status is set if the counter value is exceeded or the value 0 is reached.
The limit status is maintained until it is again cleared by the process data
(control byte) or the DTM.
Reset limit status
The limit value status is reset by enabling this field. If the "Switching
Output" parameter is selected, it is also reset.
Auto reset upon limit
If you enable this field, the counter is reset when the limit value is
exceeded (up counter = 1) or set to the initial value (down counter = limit
value set).
Toggle limit status
If this field is enabled, the limit value status is toggled between enabled
and disabled status upon reaching the counter value.
Simulation
If simulation is switched on, you can simulate all values that appear in the
process image. The display fields become input fields/checkboxes:
- Counter status
- Status Gate
- Count Direction
- Status of Limit Value Output
* Default status
Inputs and outputs assigned to the counters can be configured as shown in Section
"Parameters in the DO Mode" or "Parameters in the DI Mode".
Pos: 30.15 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1