765-1503/100-000
Commissioning
Product manual | Version: 2.0.0
79
16DO FLD EI DC 24V 2.0A
Table 47: Port-Specific Configuration Parameters
Node Name
Node Class
Access Default Description
OverCurrentPin1
Variable
Read
0
Warning level for current upper limit on pin 1;
unit: 1 mA
0: monitoring not enabled
OverCurrentPin2
Variable
Read
0
Warning level for current upper limit on pin 2;
unit: 1 mA
0: monitoring not enabled
OverCurrentPin4
Variable
Read
0
Warning level for current upper limit on pin 4;
unit: 1 mA
0: monitoring not enabled
UnderCurrentPin1
Variable
Read
0
Warning level for current lower limit on pin 1; unit:
1 mA
0: monitoring not enabled
UnderCurrentPin2
Variable
Read
0
Warning level for current lower limit on pin 2; unit:
1 mA
0: monitoring not enabled
UnderCurrentPin4
Variable
Read
0
Warning level for current lower limit on pin 4; unit:
1 mA
0: monitoring not enabled
10.3.3.1.4 Reading Port Process Values
The OPC UA server provides nodes with process data. For example, the OPC UA client
can read out the value on pin 4 of a port in the
Pin4ProcessData
node.
Process Data of the Digital Inputs and Outputs
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > SIOProcessData
Note
OPC UA client can only read process output data
The process output data is written by the EtherNet/IP scanner. The OPC UA client can
only read process output data.
The following table lists port-specific process data of the digital inputs and outputs.
Table 48: Port-Specific Process Data of the Digital Inputs and Outputs
Node Name
Node Class
Access
Description
Pin2ProcessData
Variable
Read
Process data on pin 2
Pin4ProcessData
Variable
Read
Process data on pin 4
10.3.3.1.5 Reading Measured Power Values
The OPC UA server provides nodes with calculated measured values. For example, the
OPC UA client can read out the calculated total current of supply cable 1 in the
SumCur-
rentL
node.